How to protect a solid fuel boiler from overheating and condensation

When purchasing and installing a solid fuel boiler, it is necessary to take into account the peculiarities of its operation, namely the high probability of overheating in emergency situations, which can result in a serious accident and even destruction of the water jacket of the unit (explosion). Also, considerable harm can be caused by the formation of condensation on the walls of the combustion chamber, which happens under certain operating conditions. To eliminate such troubles, the solid fuel boiler must be protected from overheating and condensation, which will be discussed in our article.

Using the Safety Valve

This is not the same thing as a safety valve. The latter simply relieves pressure in the system, but does not cool it. Another thing is the boiler overheating protection valve, which takes hot water from the system and instead supplies cold water from the water supply. The device is non-volatile and is connected to the supply and return lines, water supply network and sewerage system.

When the coolant temperature is above 105 ºС, the valve opens and, thanks to a pressure in the water supply of 2-5 Bar, hot water is forced out of the heat generator jacket and pipelines with cold water, after which it goes into the sewer. How the solid fuel boiler protection valve is connected is shown in the diagram:

The disadvantage of this method of protection is that it is not suitable for systems filled with antifreeze liquid. In addition, the scheme is not applicable in conditions where there is no centralized water supply, because along with a power outage, the supply of water from a well or pool will also stop.

What is the expansion tank for?

The expansion tank is usually installed in the attic. Most often, this room is not heated. Based on this, there is a need to insulate the walls of the expansion tank. Otherwise, in the cold season, the water in it will completely freeze. The tank compensates for changes in water temperature. In addition, water may boil in the boiler, especially if the boiler is heated too intensely. Due to the formed bubbles, the volume increases. This is what the additional volume in the expansion tank is for.


Expansion tank

It is recommended to pay attention to the release of excess water from the tank when it overflows. You will have to consider the presence of drainage into a sewer or septic tank.

Chimney requirements

To determine what characteristics the manufacturer himself presents, you need to read the instructions, because specific data is given there, what is the minimum cross-section of the pipe needed, height, temperature conditions - these factors in a particular case are fundamental and you need to focus on them. As a rule, the instructions contain the manufacturer writes which chimney is better for a solid fuel boiler and what technical parameters need to be taken into account. The above listed characteristics, such as the height and length of the chimney, will allow you to choose a reliable and, most importantly, functional channel from the point of view of this particular model.

Consider the diameter of the chimney for a solid fuel channel, because not every channel will be able to remove the formed amount of gas in a certain time, and accumulated fumes and gases can enter the room through unsealed joints and cracks.

Technological requirements

The following technical requirements must be observed:

  • A special area must be provided to disperse the smoke. It is a vertical pipe installed behind the nozzle of a solid fuel boiler. The acceleration section is made one meter high.
  • The chimney is installed only vertically. Deviation of no more than 30 degrees is allowed.
  • Deflections are prohibited.
  • The length is very important (3 - 6 meters).
  • Three horizontal sections are allowed. Moreover, the length of each should not exceed half a meter.
  • The height of the head above the roof must exceed 100 cm.
  • The pipe is attached to the wall in 1.5 meter increments.
  • To create a sealed joint, the pipes are generously lubricated with heat-resistant sealant.

To obtain ideal draft, it is necessary that the chimney design has a minimum number of turns. A straight pipe is considered best.

The chimney can be installed inside or outside the building. For the first option, it is necessary to protect the pipe so that it does not come into contact with flammable materials. A special metal screen is used, installed where the pipe passes through the ceiling. The chimney must be located at a distance of more than 25 cm from the wall.

External structures look much safer. They are much easier to maintain. Masters consider this method the most preferable.

Causes of overheating

The only reason for overheating is that the boiler produces more heat than is consumed by the heating system. But if everything was fine before, and now the boiler is overheating, then the problem is not that the boiler is very powerful, but the problem is something else.

It is possible that you simply have a clogged dirt filter in front of the circulation pump. In this case, you need to unscrew it and clean it and the problem will be solved. If you have this problem, your return will be cold.

There is an option that the circulation pump is simply broken. If you have this problem, your return will also be cold. Change the pump.

But the most common problem is overheating as a result of a power outage. Everything is perfect for you - a clean filter, a working pump, but it just can’t work. And overheating occurs. You can solve the problem by extinguishing the boiler or pulling out the burning fuel from the boiler firebox - but this is far from the best option. The best option is to make the heating system insensitive to power outages - make it gravity-fed or install an uninterruptible power supply.

Watch a video showing how the boiler overheats when the power supply is turned off.

And here is a video with a method for solving the problem of overheating of the boiler and heating system.

A true boiler repair specialist is hard to find.

Therefore, it is important to understand them yourself, because a specialist is really not always required and many problems can be eliminated yourself. Let's look at the list of boiler faults, which maximally covers all possible breakdowns

The article is intended for a non-specialist, but an ordinary person who can eliminate such problems.

In addition to the boiler, I would like to protect the washing machine, refrigerator, stereo system, air conditioner, etc.

This is the most popular option for a country house.

4.1. Stabilizer for the whole house

If one phase

(220 volts), then they usually choose a single-phase voltage stabilizer with a power of 10-12 kW, for a small house 8 kW. But more and more often, houses are connected in a three-phase way (380 volts), in which case a three-phase stabilizer is needed, approximately 15 kW or three single-phase 5 kW each. ExpertKotel.ru reminds that when connecting three-phase motors (pumps, machines, etc.) to three single-phase 5-motors, you need to purchase a Network Control Unit (BCS), which will monitor possible phase imbalance (BCS example). For a conventional three-phase stabilizer, BKS is not needed.

Actually option 4.1. This is a repetition of points 1 and 2, but on the scale of the entire house and with the nuance of three-phase stabilizers.

Which technologies should you prefer?

The most budget options are relay ones, they have average performance characteristics, example Resanta ASN-10000/1-Ts - 10 kVA (Fig. 6.) and make clicks when switching relay stages, this feature should be taken into account if the stabilizer is installed nearby from the bedroom.

Fig.6. Resanta ASN-10000/1-C is suitable for a small house with a power of all appliances up to 7-8 kW (10 kVA).

Advanced level - thyristor and triac voltage stabilizers

, for example Energy Classic 12000 (12 kVA, thyristor, Fig. 7.) and Energy PREMIUM 12000 (12 kVA, triac, Fig. 7.). They are also stepped, but thyristors operate faster than relays and do not produce unpleasant clicks. They have a longer warranty (3 and 5 years, respectively, versus 1 year for relay devices) and in general these devices are more reliable.

A less expensive thyristor stabilizer is the Volt Engineering Ampere E 9-1/50, it has excellent equipment, for example, there are filters for high-frequency and impulse noise, protection against sparking contacts on the line and an electronic bypass with a cut-off relay function, which puts the model on a par with stabilizers of professional series. It has no buzzing, no clicking, and fan cooling is activated only under heavy loads, and the price starts at RUB 32,950. (for a power of 11 kW), the warranty is also at the level of the best and is 5 years.

Only inverter stabilizers are more expensive than thyristor and triac models; their characteristics are either at the same level or significantly superior to all analogues. For example, Shtil InStab IS12000 (12 kVA) regulates parameters without delay, i.e. the response time to changes in voltage in the network is 0 ms, it works silently, the range is not achievable for other types and is 90-310 volts.

Therefore, the advice is simple: if your budget allows, you should choose from these three options, all three are extremely worthy. Below (clause 4.2.) specific examples are described for inverter, triac and thyristor models.

Fig.7. Energy Classic 12000 (thyristor, right) and Energy PREMIUM 12000 (triac, left), both at 12 kVA (~10 kW), unlike the previous one (Fig. 6.): fast power switches, small error 5% and 1 .5% respectively, more protection options and an extended warranty from the factory - 3 and 5 years.

4.2. Stabilizer for the whole house and UPS for the boiler

The essence of the method is to install a stabilizer for the whole house (previous point 4.1.) for all electrical appliances and separately install a UPS for boiler autonomy (point 3.).

  • Example 1. The house is connected to 220 volts (10 kW), Shtil appliances:
  • — Stabilizer for all devices Shtil InStab IS12000 (12 kVA, inverter, 2 years warranty) + UPS Shtil SW1000SL (1 kVA, batteries included).
  • — Budget ~81,000 rub.
  • Example 2. The house is connected to 220 volts (10 kW), Energy appliances:
  • — Stabilizer for all devices Energy Classic 12000 (12 kVA, thyristor, 3 year warranty) + Energy UPS Pro 800 (0.8 kVA) + battery 12-55 (capacity 55 Ah).
  • — Budget ~69,700 rub.
  • Example 3. The house is connected to 220 volts (10 kW), Energy appliances:
  • — Stabilizer for all devices Energy Premium 12000 (12 kVA, triac, 5 year warranty) + Energy UPS Pro 800 (0.8 kVA) + battery 12-55 (capacity 55 Ah).
  • — Budget ~81,900 rub.
  • Example 4. House connected to 380 volts (15 kW), Energy appliances:
  • — Stabilizer for all devices Energy Classic 15000-3 M (three-phase 15 kVA, thyristor, 3 year warranty) + Energy UPS Pro 800 (0.8 kVA) + battery 12-55 (capacity 55 Ah ).
  • — Budget ~102,500 rub.
  • Example 5. The house is connected to 380 volts (15 kW), Energy appliances:
  • — Stabilizer for all devices Energy Premium 15000-3 M (three-phase 15 kVA, triac, 5 year warranty) + Energy UPS Pro 800 (0.8 kVA) + battery 12-55 (capacity 55 Ah ).
  • — Budget ~137,900 rub.
  • Example 6. The house is connected to 380 volts (15 kW), Energy and Shtil appliances:
  • — Stabilizer for all devices Energy Classic 15000-3 M (three-phase 15 kVA, thyristor, 3 year warranty) + UPS Shtil SW1000SL (1 kVA, batteries included).
  • — Budget ~95,600 rub.
  • Example 7. The house is connected to 380 volts (15 kW), Energy and Shtil appliances:
  • — Stabilizer for all devices Energy Premium 15000-3 M (three-phase 15 kVA, triac, 5 year warranty) + UPS Shtil SW1000L (1 kVA) + battery module Shtil BM-36-18.
  • — Budget ~145,740 rub.
  • Example 8. The house is connected to 380 volts (15 kW), Volt Engineering and Shtil equipment:
  • — Volt Engineering Hertz E 16-3/25 (three-phase 17 kVA, triac, 5 year warranty) + UPS Shtil SW1000L (1 kVA) + battery module Shtil BM-36-18.
  • — Budget ~137,000 rub.

In examples 2,3,4,5 you need to vary the capacity and number of batteries to suit your needs; the greater the total capacity, the longer the boiler operates from the UPS when the electricity is turned off. For example, to increase the operating time, take not one small battery with a capacity of 55 Ah, but three large ones with a capacity of 200 Ah. The budget for improvements will increase significantly.

How to save money?

Clauses 3. and 4.2. suggest the possibility of savings, but saving on thyristor, triac or inverter stabilizers, as practice has shown, does not really work out (for example, in relay models, to reduce the cost of products, aluminum windings can be used instead of copper), a good assembly with high-quality components costs the corresponding production investments, which is reflected in the final cost.

But saving on a UPS is possible if we are talking only about line-interactive options, in the example it was the Energy UPS Pro 800. Its simplified analogue, the Energy UPS Garant-750, is ~25% cheaper, and the “analog analogue” Rucelf UPI-600-12 -EL is even cheaper by an additional ~20%.

  • Economy 1. UPS Energy:
  • — UPS for the boiler Energy UPS Garant-750 (power 0.75 kVA) + battery for 12-55 (capacity 55 Ah).
  • — Budget ~26,000 rub.
  • Economy 2. UPS Rucelf:
  • — UPS for the Rucelf UPI-600-12-EL boiler (power 0.6 kVA) + battery for 12-55 (capacity 55 Ah).
  • — Budget ~24,000 rub.
  • Economy 3. Rucelf UPS minimum power:
  • — UPS for the Rucelf UPI-400-12-EL boiler (power 0.4 kVA) + battery for 12-55 (capacity 55 Ah).
  • — Budget ~19,500 rub.

I want maximum opportunities, budget is not important

There are a lot of premium options on the market; here are just two sets.

  • Maximum 1. House connected to 380 volts (15 kW), appliances Energy:
  • — Energy Premium 15000-3 M (three-phase 15 kVA, triac, 5 year warranty) + Energy UPS Pro 5000 (5 kVA, 24 V) + battery 12-200 (capacity 200 Ah, 2 pcs. ., this is the minimum for such a UPS) + BKS + mounting rack 106-45-25.
  • — Budget ~266,450 rub.
  • Maximum 2. The house is connected to 380 volts (15 kW), Energy and Calm appliances:
  • — Energy Premium 15000-3 M (three-phase 15 kVA, triac, 5 year warranty) + UPS Shtil SW1000L (1 kVA) + battery module Shtil BM-36-18 + BCS + mounting rack 106-45- 25.
  • — Budget ~161,000 rub.

Circuit with heat accumulator

A number of European Union countries have introduced rules according to which schemes for connecting solid fuel boilers to the heating system must necessarily include a heat accumulator. Without it, the operation of such heaters is simply prohibited. The reason is the high content of carbon monoxide (CO) in emissions while limiting the supply of oxygen to the firebox to reduce the intensity of combustion.

With normal air access, harmless carbon dioxide (CO2) is formed, so the firebox must operate at full capacity, transferring energy to the heat accumulator. Then the CO content will not exceed environmental standards. In the post-Soviet space there are no such requirements yet; accordingly, we continue to block the air supply in order to achieve slow smoldering of wood, for example, in a long-burning boiler.

Heat accumulators are commercially available as a finished product, although many craftsmen make them themselves. By and large, this is a tank covered with a layer of thermal insulation. The factory version may have a built-in DHW circuit and heating element for heating water. This solution allows you to accumulate heat from a wood-burning boiler, and when it is idle, provide heating for the house for some time. The connection diagram of the boiler with the heat accumulator is shown in the figure:

Note. In the circuit, instead of a mixing unit consisting of several elements, a ready-made device is installed that performs the same functions - LADDOMAT 21.

What are the ways to protect heating equipment from overheating?

In order to increase the consumer attractiveness of their products, manufacturing companies try to include any guarantees of their safety in the technical passport of boiler equipment. The uninitiated consumer has no idea about the means of protecting a heating boiler from boiling.

The following methods currently exist to ensure the protection of solid fuel units used for autonomous heating systems. The effectiveness of each method is explained by the operating conditions of boiler equipment and the design features of the units.

In most cases, in the technical data sheet for a heating device, manufacturers recommend using tap water for cooling. In some cases, solid fuel heating boilers are equipped with built-in additional heat exchangers. There are models of boilers with remote heat exchangers. A safety valve is used to prevent overheating. The safety valve is designed only to relieve excessive pressure in the system, while the safety valve allows access to tap water when the boiler overheats.

Exceeding the temperature of the coolant above 100 0C creates excess pressure that opens the valve. Under the influence of tap water, which is supplied under pressure of 2-5 bar, hot water is forced out of the circuit by cold.

The first aspect that causes controversy about cooling with tap water is the lack of electricity to operate the pump. The expansion tank does not contain enough water to cool the boiler.

The second aspect that this cooling method rejects is related to the use of antifreeze as a coolant. If an emergency occurs, up to 150 liters of antifreeze will go into the sewer along with the incoming cold water. Is this method of protection worth it?

The presence of a UPS will allow you to maintain the operation of the circulating pump in a critical situation, with the help of which the coolant will evenly disperse through the pipeline without having time to overheat. As long as the battery capacity lasts, the uninterruptible power supply guarantees the operation of the pump. During this time, the boiler should not have time to heat up to critical parameters; the automation will work, running water through a spare, emergency circuit.

Another way to get out of a critical situation would be to install an emergency circuit in the piping of a solid fuel unit. Switching off the pump can be duplicated by the operation of a spare circuit with natural coolant circulation. The role of the emergency circuit is not to provide heating for residential premises, but only to be able to remove excess thermal energy in an emergency.

This scheme for organizing the protection of the heating unit from overheating is reliable, simple and easy to use. You will not need any special funds for its equipment and installation. The only conditions for such protection to work are:

  • the presence of an expansion tank or storage tank in the system;
  • use of a petal type check valve only;
  • the secondary circuit pipes must be larger in diameter than the conventional heating circuit.

Thermostat and stabilizer - devices that help you save

Temperature regulators and stabilizers are automatic equipment, without which an electric heating boiler for a home will not be able to fully operate. These devices belong to different types of equipment, but together they can significantly save your budget. On the modern market you can find automation in any price category and with a different set of functions. The main selection criterion is the durability and functionality of the purchase.

The widespread use of boiler equipment operating on solid fuels poses special requirements for owners of private houses. Despite technical progress, which has made it possible to bring modern solid fuel heating devices to perfection, the operation of such equipment carries a certain danger. Malfunctions and violations of the operating conditions of heating equipment can cause equipment failure at the height of the heating season. In the worst case, the occurrence of emergency situations with a working unit can result in serious injuries to the inhabitants of the house and damage to residential buildings.

In this aspect, one of the most important conditions for safe operation will be the protection of the solid fuel boiler from overheating. Strict adherence to safety rules for the operation of heating equipment, the presence of capable automation and control devices will provide you with the necessary protection from unforeseen situations.

Let's take a closer look at what the protection of boiler equipment from overheating is based on. What could be causing the boiling of the coolant in a heated circuit and what are the consequences of such an emergency.

How does a thermostatic distribution valve work?

The thermostatic valve is installed on the supply in front of the bypass section (pipeline section) connecting the supply and return of the boiler in close proximity to the boiler. This creates a small coolant circulation circuit. The thermoflask, as mentioned above, is installed on the return pipeline in close proximity to the boiler.

At the moment of boiler startup, the coolant has a minimum temperature, the working fluid in the thermoflask occupies a minimum volume, there is no pressure on the thermohead rod, and the valve allows the coolant to flow only in one direction of circulation in a small circle.

As the coolant heats up, the volume of the working fluid in the thermoflask increases, the thermal head begins to put pressure on the valve stem, passing the cold coolant to the boiler, and the heated coolant into the general circulation circuit.

As a result of mixing cold water, the temperature in the return line decreases, and, therefore, the volume of the working fluid in the thermal flask decreases, which leads to a decrease in the pressure of the thermal head on the valve stem. This in turn leads to the cessation of the supply of cold water to the small circulation circuit.

The process continues until the entire coolant is heated to the required temperature. After which the valve blocks the movement of the coolant through the small circulation circuit, and the entire coolant begins to move through the large heating circle.

The thermostatic mixing valve works in the same way as a distribution valve, but it is installed not on the supply pipe, but on the return pipe. The valve is located in front of the bypass, connecting the supply and return and forming a small circle of coolant circulation. The thermostatic flask is mounted in the same place - on a section of the return pipeline in close proximity to the heating boiler.

While the coolant is cold, the valve allows it to flow only in a small circle. As the coolant heats up, the thermal head begins to put pressure on the valve stem, allowing part of the heated coolant to pass into the general circulation circuit of the boiler.

As you can see, the scheme is extremely simple, but at the same time effective and reliable.

The thermostatic valve and thermal head do not require electrical energy to operate; both devices are non-volatile. No additional devices or controllers are needed either. To heat the coolant circulating in a small circle, 15 minutes are enough, while heating the entire coolant in the boiler can take several hours.

This means that using a thermostatic valve, the duration of condensation formation in a solid fuel boiler is reduced several times, and along with it, the time of the destructive effects of acids on the boiler is reduced.

To protect a solid fuel boiler from condensation, it is necessary to properly piping it, using a thermostatic valve and creating a small coolant circulation circuit.

When purchasing and installing a solid fuel boiler, it is necessary to take into account the peculiarities of its operation, namely the high probability of overheating in emergency situations, which can result in a serious accident and even destruction of the water jacket of the unit (explosion). Also, considerable harm can be caused by the formation of condensation on the walls of the combustion chamber, which happens under certain operating conditions. To eliminate such troubles, the solid fuel boiler must be protected from overheating and condensation, which will be discussed in our article.

What else is needed in the system

The boiler piping will be incomplete if it does not have a tap to drain and fill the system. And it is better if they are separate. The specific installation location depends on the structure of the system, but there are certain rules:

  • The drain tap is installed at the lowest point. This is very important if the heating system needs to be preserved for the winter - it is necessary that as little coolant remains in it as possible. If the system will operate constantly in winter, a tap (with or without a pipe) is usually attached to one of the radiators. This will be the place where the system drains.


    Such a valve for draining the system can be installed in any convenient place (on the return pipeline)

  • If the heating system will use water, an inlet from the water supply is usually connected. In the case of a wall-mounted gas boiler, there is a special pipe with a stationary tap for this. Cold water is connected to this input; if refilling is necessary, the tap is opened for a short time. If a boiler without a special pipe is used, a tap is also installed in the supply pipeline (preferably higher). Alternatively, on a section of pipe that goes to the expansion tank.


    One of the options for installing a tap for filling the heating system

In some systems, the drain and fill of the system are made from one tap. This is possible if there is a pump that pumps the coolant and there is a pressure gauge by which you can control the pressure created. If there is a separate tap for filling the system at a high point, it can be filled by gravity.

Basic wiring diagram for a solid fuel boiler

For a better understanding of the processes that occur during operation of the heat generator, we will show its wiring in the figure, and then analyze the purpose of each element. In the case when the heating unit is the only heat source in the house, it is recommended to use the following basic diagram to connect it:

Note. The basic diagram, where there is a small boiler circuit and a three-way valve, shown in the figure, is mandatory for use when working together with other types of heat generators.

So, the first thing on the path of coolant movement from the boiler installation is the safety group. It consists of three parts installed on one manifold:

  • pressure gauge - to control the pressure in the network;
  • automatic air release valve;
  • safety valve.

When operating a solid fuel boiler, there is always a risk of overheating of the coolant, especially at modes close to maximum power. This is due to a certain inertia of fuel combustion, because when the required water temperature is reached or there is a sudden power outage, it will not be possible to immediately stop the process. Within a few minutes after the air supply is stopped, the coolant will still heat up, at which point the risk of steam formation arises. This leads to an increase in pressure in the network and the danger of destruction of the boiler or burst pipes.

To avoid emergency situations, the piping of a solid fuel boiler must include a safety valve. It is adjusted to a certain critical pressure, whose value is indicated in the heat generator’s passport. As a rule, the value of this pressure in most systems is 3 Bar; when it is reached, the valve opens, releasing steam and excess water.

Further, in accordance with the diagram, for proper operation of the unit it is necessary to organize a small coolant circulation circuit. Its task is to prevent cold water from the home heating system from entering the heat exchanger and water jacket of the boiler. This is possible in 2 cases:

  • when starting heating;
  • When the pump stops due to a power outage, the water in the pipelines cools down, and then the voltage supply is restored.

Important! A power outage situation poses a particular danger to cast iron heat exchangers. A sudden pump supply of cold water from the system can lead to its cracking and loss of tightness.

If the firebox and heat exchanger are made of steel, then connecting the solid fuel boiler to the heating system through a three-way valve protects them from low-temperature corrosion. The phenomenon occurs when condensation forms on the inner walls of the combustion chamber due to temperature differences. Mixing with volatile fractions and ash, moisture forms a layer of scale on steel walls, which is very difficult to clean off. In this case, the metal is subject to corrosion and the service life of the product as a whole is reduced.

The scheme works on the following principle: while the water in the boiler jacket and in the system is cold, the three-way valve allows it to circulate through a small circuit. After reaching a temperature of 60 ºС, the unit begins to mix coolant from the network at the inlet of the unit, gradually increasing its flow rate. Thus, all the water in the pipes warms up gradually and evenly.

Determining the probability of condensation formation

Calculations can be carried out if condensation is formed as a result of a large release of steam and overheating of the chimney walls, and the power of the operating equipment is known. The average rate of heat release is 1 kW per 10 sq. m.

The formula is relevant for rooms with ceilings below 3 m:

MK = S*UMK/10

MK - boiler power (kW);

S is the area of ​​the building where the equipment is installed;

WMC is an indicator depending on the climate zone.

Indicator for different climatic zones:

  • south - 0.9;
  • north - 2;
  • middle latitudes - 1.2.

When operating a double-circuit boiler, the resulting MK indicator should be multiplied by an additional coefficient (0.25).

The basic principle of protecting the boiler from condensation

To protect a solid fuel boiler from the formation of condensation, it is necessary to eliminate the situation in which this process is possible. To do this, do not allow cold coolant to enter the boiler. The return temperature should be 20 degrees less than the supply temperature. In this case, the supply temperature must be at least 60 C.

The simplest method is to heat a small amount of coolant in the boiler to the nominal temperature, create a small heating circuit for its movement and gradually add the rest of the cold coolant to the hot water.

The idea is simple, but it can be implemented in various ways. For example, some manufacturers offer to purchase a ready-made mixing unit, the cost of which can be 25 000

and more rubles.
For example, the FAR company (Italy) offers similar equipment for 28,500 rubles
, and the
Laddomat
sells a mixing unit for
25,500 rubles
.

A more economical, but no less effective way to protect a solid fuel boiler from condensation is to regulate the temperature of the coolant supplied to the boiler using a thermostatic valve with a thermal head.

Why is the riser hot and the batteries cold?

Sometimes, with a hot supply, the return of the heating battery still remains cold. There are several main reasons for this:

  • installation was performed incorrectly;
  • the system or one of the risers of a separate radiator is airborne;
  • insufficient fluid flow;
  • the cross-section of the pipe through which the coolant is supplied has decreased;
  • The heating circuit is dirty.

Cold return is a serious problem that must be eliminated. It entails many unpleasant consequences: the temperature in the room does not reach the desired level, the efficiency of radiators decreases, and there is no way to correct the situation with additional devices. As a result, the heating system does not work as it should.

The main trouble with cold return is the large temperature difference that occurs between the supply and return temperatures. In this case, condensation appears on the walls of the boiler, reacting with carbon dioxide, which is released during fuel combustion. As a result, acid is formed, which corrodes the walls of the boiler and shortens its service life.