How and why the Lemax gas boiler goes out: how to turn it on and make adjustments, as well as connecting the room thermostat

Lemax gas boilers seriously compete with their European counterparts.

They are assembled from spare parts manufactured by recognized leaders in the production of heating equipment - Vaillant, Sit and other well-known manufacturers.

With excellent quality, the cost of Lemax boilers is two or more times lower than that of the “Europeans”.

Basically, this is achieved by eliminating all additional devices and components from the design, leaving only the most necessary elements.

This has a positive effect on the performance of the units, reduces the frequency of breakdowns or failures, but some malfunctions still occur.

Operating instructions for the Lemax gas boiler

For proper operation of the device, you must follow the rules of its operation.
First of all, you should pay attention to the room in which you plan to install it. It must be spacious, at least 8 m², and well ventilated

To install a floor-standing model, in order to prevent the floor from catching fire, the following rules must be observed:

  • lay a sheet of non-flammable heat-insulating material at the installation site;
  • on top of it is a sheet of iron and only then a cauldron.

In this case, it is worth considering the distance of the device body from the walls: at least 150 mm at the rear, 100 mm at the sides and 1000 mm at the front. The boiler is connected to the gas main using threaded pipes, which will allow it to be disconnected if necessary.

Important! The Lemax boiler requires the presence and connection to a chimney facing the street

Advantages and disadvantages

Every year, Lemax specialists develop and produce new varieties of gas boilers and other heating devices. At the same time, there is a consistent increase in their quality and improvement in technical characteristics. To assemble boiler equipment, the best components made in Germany, Austria and Italy are used. This is the reason for a noticeable increase in the quality of these products.

Like any other appliances, Lemax gas boilers have strengths and weaknesses. They are characterized by energy independence, wear resistance, overheating protection, good power and high efficiency. The product is guaranteed for 3 years. Heating appliances from this manufacturer are presented in several models that differ in their technical characteristics.

List of positive characteristics of the Lemax boiler:

  • Energy independence.
  • Durability.
  • Reliability.
  • Easy to use.
  • Affordable price.
  • Convenience of the procedure on how to start a Lemax boiler.

Gas boilers from this company are wall-mounted and floor-mounted. Wall-mounted models include only one series of this equipment. The range of floor-standing models is more extensive - there are six of them. Each variety is characterized by good service life, reliability, simplicity of design and low cost.

Turning on the gas boiler

A prerequisite for warranty service of a gas boiler is that the first switch-on must be carried out exclusively by a specialist from the gas service. If the user follows all instructions and safety precautions when starting up independently, then you can also count on the reliability and durability of the heating system.

The initial start-up of a wall-mounted boiler is carried out strictly after checking the following points.

The first thing you need to do is make sure that the gas pipes are tight when the gas valve is closed and open. If gas flow is not recorded within 10 minutes after connecting all pipes, then it can be stated that the system is sealed.

The gas supplied from the main pipeline must meet the requirements specified in the instructions for the boiler. When transferring the unit to process a liquefied mixture, you need to change the nozzles in advance.

You also need to check the pressure level in the system. It should be as recommended. The air intake and carbon dioxide exhaust pipes should be checked for blockages.

Sometimes users encounter the problem of poor circulation of the pump. Often the cause is low mains voltage. This problem is solved by installing a stabilizer

It is necessary to make sure that the room with the boiler has a working ventilation system. Additionally, the smoke pressure safety switch is checked.

After carrying out the preliminary work, the procedure for starting the boiler follows:

  • The gas boiler is connected to the network, the gas supply to the device is opened;
  • Check that all valves at the inlet and outlet of the coolant into the unit are open;
  • Press the button or turn the switch on the boiler dashboard depending on the switching method specified in the instructions.

You can adjust the temperature using the corresponding buttons. Working in automatic mode, the boiler independently turns on the burner if it is necessary to heat the water in the system. If the boiler is double-circuit, then when hot water is turned on, the burner automatically turns on for heating.

On the boiler display, after the initial start-up, it is recommended to configure all boiler parameters. The instructions usually indicate the sequence of necessary actions.

The interlock system cuts off the gas supply if the burner does not ignite within approximately ten seconds. When starting for the first time, it may be necessary to remove the ignition lock due to the presence of air in the gas line. You need to wait until the air is replaced by gas. The lock is removed when the device is restarted.

To start a floor-standing gas boiler, you need to carry out the same preparatory procedures as for a wall-mounted one. Before starting up, you need to ventilate the boiler room, make sure that all heating pipe taps are open and that there is draft in the chimney. You can check the traction using a piece of paper.


There are two options for turning off a floor-standing gas boiler. You can turn off only the main burner or the main burner together with the pilot

Switching on the floor-standing boiler:

  • The door of the device is opened, the position of the boiler control knob is checked in the off position.
  • The gas supply valve opens.
  • The control knob is set to the piezo ignition position.
  • Next, press the handle for 5 - 10 seconds so that the gas passes through the pipes and displaces the air. The piezo ignition button is pressed.
  • Then the presence of a flame in the burner is checked. If the burner does not light, the procedure is repeated.

After igniting the main burner, you can use the control knob to adjust the heating temperature.

Why does the device go out?

There may be several reasons why the burner goes out:

  • Stopping the gas supply. Turn off the boiler and wait until the supply is restored.
  • Unstable or absent voltage in the power supply network (for volatile Lemax boilers).
  • Failure or activation of the traction sensor. We need to check whether it is there and whether the chimney is clogged. Sometimes cleaning the sensor contacts helps.
  • The thermocouple contacts have oxidized and do not close. It should be cleaned with fine-grained sandpaper.
  • Reverse, insufficient or excessive draft. The draft sensor responds to all situations by turning off the burner.

Problems with traction are most common in non-volatile installations, where the stability of the unit’s operation depends on it.

If the draft is too weak, the sensor turns off the burner due to the possibility of smoke in the room.

Excessive draft is dangerous due to the possibility of the flame on the burner exploding, which will provoke the supply of gas into the room with unpredictable consequences. Therefore, an increase in draft against the set value is also an emergency event, leading to the boiler stopping.

User manual

There is no doubt that Lemax boilers can show their best side. But a lot depends on the consumers themselves, whether they comply with the instructions or not

And the most important thing begins even before the moment when there is a need to light the installed boiler. It is required to choose strictly equipment that matches the power of the heated room

Since exceeding the operating pressure is very dangerous, it is imperative to install a relief valve and set it properly.

The following actions are not allowed:

  • introducing water into the system while the combustion chamber is running, as well as after it is stopped - until the coolant cools to less than +50 degrees;
  • using a boiler when circulating coolant cooled to +50 degrees or less;
  • use of heating devices with automatic components without grounding;
  • installation of gas boilers, their commissioning, prevention and any technical manipulations by persons who do not have official permission;
  • the use of devices in conjunction with smoke ducts that do not correspond to them;
  • covering ventilation duct grilles.

You can turn on any boiler from the “Premium” collection or another series only after connecting it to the chimney; be sure to also prevent it from blocking and disrupting normal draft. You should also check that the entire heating system is filled with water, that it is not blocked anywhere by valves or air pockets. In the event of a serious failure of the automation, you should immediately turn off the boiler, and also leave all attempts to start it until the defects are eliminated by professionals. If the coolant warms up to more than +95 degrees, the boiler is also turned off and the cause of overheating is eliminated independently or with the help of hired specialists.

In advance, at the stage of selecting and installing equipment, it is necessary to prepare high-quality natural ventilation. It is recommended to install a steel sheet not only in front of the firebox, but also under the boiler itself, as well as around it around the perimeter.

If there was already a boiler or stove installed before, then during installation without replacing pipes and radiators, they should be washed. Violation of this requirement means that all claims regarding pipe capacity, heating of the coolant and the room, and water circulation will not be accepted. When starting up a gas boiler, first turn the knob and only after that start adjusting and starting. The time to initiate gas ignition ranges from 10 to 60 seconds, depending on a number of parameters that are unpredictable in a particular case. After the end of the annual heating phase, you cannot drain the water from the boiler itself and the heating lines - this threatens rapid and severe corrosion.

Kinds

The “Premium” line is made of first-class steel, its thickness is 0.2 cm. The grade of steel used is DC01, it fully complies with Russian, European and even North American quality standards.

The main technical characteristics are as follows:

  • generated power 7.5-10 kW (for closed systems with a pressure of 1 atm);
  • generated power from 12.5 to 60 kW (in systems with pressure up to 3 atm);
  • a special enamel coating with anti-corrosion characteristics that works effectively when heated to 750 degrees;
  • coating the heat exchanger with a reagent that blocks the action of mineral oil and salts dissolved in water;
  • autonomy of use;
  • unique design of the gas burner and valve;
  • prevention of excessive heating and stopping traction;
  • ease of cleaning;
  • maximum efficiency.

Heating efficiency is increased due to increased air supply in the primary and secondary circuits, as well as thanks to a volumetric heat exchanger and long-term retention of flue gases. Hot water supply is provided in systems designed for a minimum of 12.5 kW. Conversion of equipment to liquefied gas fuel is allowed. Weight varies from 39 to 125 kg. The “Patriot” selection is made based on both gravitational and forced circulation of the coolant; connection to the electrical network is not necessary.

The “Patriotic” series is made of strong steel and is used without a chimney. The boiler must receive air from the outside. The shape of the heat exchanger is rectangle. The generated thermal energy ranges from 6 to 20 kW, the fuel burns in a completely closed compartment. To complete the burner, Italian parts produced by world-famous concerns are used.

Smoke removal is quite reliable. An inspection port is provided to monitor the main and pilot burners. The boiler casing can be easily removed, which greatly facilitates service. Smoke removal is provided by structures made of stainless steel. Company warranty – 36 months. The efficiency of the devices is 87%, the exhaust gases are heated to at least 110 degrees.

The nominal gas pressure is 1.3 kPa, and the operating pressure in the water line is limited to 0.2 MPa. Depending on the modification, the hourly gas consumption ranges from 0.38 to 1.2 cubic meters. m. All boilers in the series heat water up to 90 degrees, the size of the coaxial chimney is 25 or 31 cm in diameter, 33-80 cm in length. Connection is made through gas pipes with a cross section of 0.5 inches; Connected pipes can be 1-1.5 inches larger

The manufacturer promises that the boiler will demonstrate excellent anti-corrosion characteristics and provide decent heat output. There is no need to connect it to the electrical network. The typical power range includes 16-50 kW. Permissible operating pressure is 4 bar, efficiency is 0.91. Measures are taken against the occurrence of soot and excessive heating.

AOGV of this series is invariably equipped with a thermomanometer, which allows you to control the pressure in the system as comfortably as possible. The design, as in other models, allows you to switch to liquefied gas, and the general warranty is 3 years. Automation through Novosit components means that the thermostat is located on the front panel. All temperatures are clearly provided there, so choosing the appropriate mode is extremely simplified.

The category of floor-standing boilers includes “Gazovik”; this selection works great when receiving thermal energy from 6 to 29 kW

The Lemax single-circuit boiler can be equipped with either a cast iron heat exchanger (in the Leader and Wise collections) or a steel one - these are Premium, Gazovik, Forward. The simplicity of the design and the opportunity to save significantly will please all responsible consumers. The parapet type of boilers is represented by all Patriot modifications - these are models 6, 7.5, 10, 12.5, 16, 20. The efficiency of all these designs is 87%, they are capable of heating water up to 90 degrees. The weight of the products varies from 42 to 67 kg depending on the modification.

Gazovik


Forward


Wise

Catalytic emitters

The key feature of gas burners with catalytic emitters is their extremely high efficiency, which reaches almost 100%. To make the heating element, fiberglass is used, which is subsequently coated with a platinum layer.

Catalytic heaters are fireproof and environmentally friendly - fuel burns without open fire, so there are no harmful emissions. The working process is almost silent, and the air heating rate is quite high, so the entire volume of the tent heats up very quickly.

The cost of such devices directly depends on their power, and the difference in price can be quite noticeable. In addition, the catalytic safe tent heater only works on branded cartridges, for which you also have to pay.

What causes blood pressure to drop?

The opposite situation (lower pressure) indicates leaks. To identify them, you will have to completely check the heating system. Inspect pipes, connections, gaskets, and other external elements.

If there are no difficulties with them, the reason may lie in the boiler itself. Typically, faults lie in the heat exchanger. Cracks and breaks periodically appear in joints when there is a constant temperature difference.

Another possible weak point is in the pressure relief valve. Sometimes it fires erroneously or remains open.

Important Operating Instructions

In terms of operation, gas boilers with a closed combustion chamber are considered safer. Their firebox does not communicate with the room air. However, the power of such boilers is significantly inferior to the power of boilers with an open combustion chamber. Therefore, in private households a second type of boiler is often installed.


The choice of future coolant depends on the goals and operating conditions of the system. If the boiler is expected to be turned off frequently, then it makes sense to think about using antifreeze

The operation of such boilers requires compliance with safety precautions. So, to install a powerful floor-standing boiler, it is customary to use a separate room with a certain size. The boiler is mounted at some distance from the walls. Nearby walls should be protected with fire-resistant material to prevent fire.

A ventilation system must be installed in the boiler room. There should also be a source of natural light. The width of the entrance door must be at least 80 centimeters. The chimney is laid in accordance with the instructions for the boiler and from heat-resistant material. The chimney must rise above the roof ridge by at least half a meter.

One safety measure is to install carbon monoxide detectors. The gas detector will promptly detect the leak of a volatile toxin and warn users about it. It can also be configured so that the ventilation is automatically turned on and the gas supply is turned off. Modern automation allows the implementation of a variety of smart systems.

If the temperature, pressure or gas sensor fails, you must immediately turn off the boiler and call a service technician. Using a boiler without these devices is fraught with serious negative consequences.

SNiP requirements state that a gas boiler must be connected to the main line using a copper pipe or a bellows hose. In this case, a faucet must be installed

If signs of a gas leak are detected, you must immediately turn off the gas tap and open the windows to ventilate the room. Do not turn on the light and try to illuminate the room by lighting matches or a lighter.

The gas boiler must be serviced at intervals specified by the manufacturer. Information about the necessary procedures is indicated in the instructions for the device. For example, you need to clean the chimney, remove scale from the heat exchanger, or clear the fumes from the burner. Then the boiler will last a long time, and the risk of serious malfunctions will be significantly reduced.

When using a gas device, do not turn it on at maximum power for a long time. This may result in the release of steam, which is unacceptable.

Sometimes the boiler begins to make unusual noises and vibrations. This may be due to the operation of the fan. We warn you that all actions that require disassembling the boiler casing automatically deprive the owner of the right to warranty repair or replacement.

However, the owner of the unit needs to monitor the operation of mechanisms and systems that protect the boiler from fire. It is necessary to maintain the temperature in the circuits at around 50 degrees, which significantly reduces the likelihood of mineral deposits forming on the internal surfaces of pipes and devices.

Doesn't start (ignite)

The unit is ignited according to a certain pattern. It does not always start the first time, and this is quite normal. But, if after repeated attempts the boiler does not ignite, it is necessary to check the condition of the components responsible for ignition.

Possible reasons could be:

  • Failure of the electronic or mechanical ignition system. It is necessary to replace the system, or clean the thermocouple contacts.
  • There is no voltage in the power supply network (for volatile units).
  • The valve on the gas supply pipe is closed.
  • The gas pressure in the system does not correspond to the nominal values.
  • The main burner nozzles are clogged. It is necessary to clean them and start the boiler.

All these reasons are the most common, but far from the only possible ones. Any malfunction in the system can negatively affect the ignition of the boiler .

NOTE!

If you have tried all the options, but the problem is not solved, you need to call a technician from a service organization.

Wood stove for home heating

Brick stoves are a traditional Russian way of heating homes.

The oldest method of heating a residential home is using a wood stove. Traditionally, such a stove was made of brick. In modern houses, firewood is more often used to start a fire, and then coal, peat or some other fuel is loaded into the firebox. Firewood is also used to maintain fire in fireplaces, which serve more to create comfort than to fully heat a residential building consisting of several rooms. Thus, a wood stove is almost an anachronism, and this type of fuel is usually used in combination with some other type to heat a house.

Finding a good stove maker these days is quite difficult. But it is necessary to lay out a brick oven in compliance with the finest nuances.

Decoding

The factory interpretation of error E25—reduced coolant circulation—does not provide a complete understanding of the essence of the problem. In the instructions for various models of the Baxi boiler, the emphasis is on blocking the pump. But this is not the only reason such a fault code appears on the display.

Control panel for gas boiler Baxi LUNA 3 comfort

Error e25 indicates an intense increase in temperature in the heating circuit. This parameter in Baksi units is determined by the difference in readings from sensors installed at the inlet and outlet of the boiler heat exchanger. When it grows at a speed above 1 0С/sec, the operation of the unit is blocked by the protection circuit. A decrease in fluid circulation is caused by several factors, therefore there is no clear recommendation for eliminating error E25. The algorithm of actions given in the article will allow you to figure out the reason for the appearance of this fault code in a short period of time.

How to start a gas boiler: preparation

There are simple instructions explaining how to start the gas boiler shown in the photo. The initial start-up is carried out when the installation and wiring of all elements of the heating equipment is completed, and the correctness of the work has been verified by the relevant authorities.

The location of the heating unit must be selected in accordance with safety standards and regulations that prevent fires. The boiler must be located at a certain distance from the wall, which depends on the manufacturer's recommendations. By the way, for some models of gas appliances this requirement is not relevant. You should also make sure that there are no flammable materials or objects nearby.

When solving the problem of how to start a gas boiler, special attention should be paid to the supply of pipes from the gas main. They do not carry out this installation work themselves, but invite specialists from the relevant services who are involved in connecting, sealing and, if necessary, installing a gas meter

After this, the boiler is connected to the chimney pipe, in which the draft and its performance are checked. She must go outside. The installation work to install the chimney depends on the type of heating device.

When preparing for startup, the boiler is disconnected from the power supply to fill it and the heating system with cold water. Then they check for leaks, turn the thermostat to the maximum value so that the operating mode switch lights up in automatic mode.

Review of the most popular series

The “line” of products is shown in the table below.

Device series:Peculiarities:
Main.These are Baksi double-circuit wall-mounted gas heating boilers, which are distinguished by their very compact dimensions. The plant was able to achieve such compactness through the use of special bimetric heat exchangers. Models of this series are perfect for installation in apartment buildings and in rooms where there is a shortage of space.
Eco.The series is distinguished by the fact that the price of the products is quite affordable, but the quality is high. “Representatives” of this line can be either single-circuit or double-circuit. The main feature is the ability to connect an external boiler and a very high-speed circulation pump. In addition, it is worth noting that the operating instructions for equipment labeled “Eco” imply that the units can operate almost autonomously. To do this, you just need to purchase an additional battery, which will power the automation in the event of a power outage.
Luna.The heaters, as in the previous case, are wall-mounted, and are available with both one and two circuits. A distinctive feature is the possibility of high-quality and very accurate self-diagnosis, that is, the liquid crystal display displays all the information on the current work process.
Nuvola.These are also wall-mounted units, but with a built-in storage tank, the volume of which is usually 60 liters. This reserve allows you to consume about 450 liters of hot water within half an hour.
Slim.These are already floor-standing solutions - they can be made with either one circuit or two (double-circuit solutions are usually equipped with a boiler with a separate pump for pumping water into the storage tank). The heat exchanger in this series is made only of cast iron. The direct purpose of models of this modification is the heating of private houses with a large area. Possible power is from 15 to 60 kW. At the same time, the maximum width of the units is only 35 cm.

As for radiators, the batteries of this company have the following properties:

  • The pressure at which the metal begins to collapse is 34 bar.
  • The possible coolant temperature is about 110 degrees. This means that it is permissible to use not only water, but also any antifreeze in the system.

Antifreeze for heating

  • Excellent level of heat transfer. This is possible due to the characteristics of the aluminum alloy from which the radiators are made, as well as due to the oval shape of the internal channels through which the coolant passes.
  • Light weight and, of course, corrosion resistance. Thanks to the first quality, the batteries can be hung on walls with low load-bearing capacities, and the second property ensures a long service life.

Baksi batteries

In principle, we have sorted out the classification of products, now it is worth considering the list of problems that you may encounter if you operate a Baxi gas heating boiler.

Starting the boiler after the summer. Stages of the first start-up of a gas boiler

After purchasing a gas device, the question arises of how to start a gas boiler. The first start is performed after the unit is installed and all communications are connected to it. Installation must be carried out in accordance with all norms and regulations.

Representatives of the gas supply company must be present when the unit is started.

Stages of starting a gas boiler

Answering the question of how to properly start a gas boiler, it should be said that the gas heating system is turned on step by step in accordance with the instructions.

Filling with water

First, fill the heating system with water. To do this, a special valve is unscrewed at the bottom of the unit. By unscrewing it, they begin to supply water to the pipes and radiators. At the same time, it is necessary to monitor the pressure gauge. The pressure should be at 2 atm.

If the first start-up of the unit occurs during the cold season, then it is advisable to preheat the room to 18-20ºC.

When the required pressure inside the system is reached, the air remaining inside the radiators and pipes should be released.

Bleeding air

Excess air accumulated in radiators reduces their heat output, so it is important to get rid of it immediately. To effectively release air, during installation of the system, each radiator should be equipped with a Mayevsky valve

They are very convenient for removing excess oxygen from certain areas. When you open a tap, you can usually hear hissing and whistling noises. If instead of hissing water begins to come out, then there is no air lock in this place

To effectively release air, during the installation of the system, each radiator should be equipped with a Mayevsky valve. They are very convenient for removing excess oxygen from certain areas. When you open a tap, you can usually hear hissing and whistling noises. If instead of hissing water begins to come out, then there is no air lock in this place.

After releasing air, the pressure may drop, so you should check the pressure gauge and add coolant if necessary.

Sometimes the problem is trapped air inside the pump. Some devices are equipped with an automatic reset system. But usually it is not very effective, so before starting it is better to perform this manipulation manually:

  1. Remove the front cover from the housing, find the pump - its location is indicated in the instructions.
  2. To bleed air from the circulation pump, plug the boiler into a power outlet and start heating the water. A noise like gurgling sounds may appear - this is how the air makes noise.
  3. Take a screwdriver and unscrew the plug. When water starts flowing, the plug must be installed back. This manipulation should be done several times until the gurgling disappears.

After releasing air from the circulation pump, check the pressure gauge reading. If the pressure has dropped significantly, it should be increased.

Pressure testing and flushing of the system

It would not be superfluous to carry out pressure testing and flushing of the heating system. After these procedures, the user will be confident that the inside of the pipes is clean and there are no leaks.

Pressure testing is done to ensure there are no leaks. To perform this, a pressure pump is required. With its help, air or water is pumped under pressure, then a break is taken for 10 minutes. If after pressure testing the pressure does not decrease, then the system is reliable and sealed. If the indicator has decreased, you should look for the “weak spot” and eliminate the leak.

Flushing is performed to clean the heating system of all contaminants and debris. To do this, open all the taps on the batteries, place containers under them and supply water under a pressure of 4 bar. The flow of water will cleanse the system of rust and sediment. For heavily contaminated radiators, flushing is carried out several times.

First start

The first start-up of a gas boiler must be carried out by a gas service specialist. You can do the preparatory work before starting the gas heating boiler yourself, but connecting the gas main must be carried out by a specialist - a gas fitter. Subsequently, if everything went well, he issues a certificate that allows you to operate the gas boiler.

For automated models, for example, “Vailant”, “Beretta”, “Ferroli”, starting involves the following sequence of actions: plugging in, opening the gas valve, pressing the start button, setting the required temperature.

When piezo ignition, hold down the flame regulator for a few seconds, then press the ignition button.

How to turn on a Lemax boiler

Operating instructions for the Lemax gas boiler

For proper operation of the device, you must follow the rules of its operation.
First of all, you should pay attention to the room in which you plan to install it. It must be spacious, at least 8 m², and well ventilated

To install a floor-standing model, in order to prevent the floor from catching fire, the following rules must be observed:

  • lay a sheet of non-flammable heat-insulating material at the installation site;
  • on top of it is a sheet of iron and only then a cauldron.

In this case, it is worth considering the distance of the device body from the walls: at least 150 mm at the rear, 100 mm at the sides and 1000 mm at the front. The boiler is connected to the gas main using threaded pipes, which will allow it to be disconnected if necessary.

Important! The Lemax boiler requires the presence and connection to a chimney facing the street

Turning on the gas boiler

A prerequisite for warranty service of a gas boiler is that the first switch-on must be carried out exclusively by a specialist from the gas service. If the user follows all instructions and safety precautions when starting up independently, then you can also count on the reliability and durability of the heating system.

The initial start-up of a wall-mounted boiler is carried out strictly after checking the following points.

The first thing you need to do is make sure that the gas pipes are tight when the gas valve is closed and open. If gas flow is not recorded within 10 minutes after connecting all pipes, then it can be stated that the system is sealed.

The gas supplied from the main pipeline must meet the requirements specified in the instructions for the boiler. When transferring the unit to process a liquefied mixture, you need to change the nozzles in advance.

You also need to check the pressure level in the system. It should be as recommended. The air intake and carbon dioxide exhaust pipes should be checked for blockages.

Sometimes users encounter the problem of poor circulation of the pump. Often the cause is low mains voltage. This problem is solved by installing a stabilizer

It is necessary to make sure that the room with the boiler has a working ventilation system. Additionally, the smoke pressure safety switch is checked.

After carrying out the preliminary work, the procedure for starting the boiler follows:

  • The gas boiler is connected to the network, the gas supply to the device is opened;
  • Check that all valves at the inlet and outlet of the coolant into the unit are open;
  • Press the button or turn the switch on the boiler dashboard depending on the switching method specified in the instructions.

You can adjust the temperature using the corresponding buttons. Working in automatic mode, the boiler independently turns on the burner if it is necessary to heat the water in the system. If the boiler is double-circuit, then when hot water is turned on, the burner automatically turns on for heating.

On the boiler display, after the initial start-up, it is recommended to configure all boiler parameters. The instructions usually indicate the sequence of necessary actions.

The interlock system cuts off the gas supply if the burner does not ignite within approximately ten seconds. When starting for the first time, it may be necessary to remove the ignition lock due to the presence of air in the gas line. You need to wait until the air is replaced by gas. The lock is removed when the device is restarted.

To start a floor-standing gas boiler, you need to carry out the same preparatory procedures as for a wall-mounted one. Before starting up, you need to ventilate the boiler room, make sure that all heating pipe taps are open and that there is draft in the chimney. You can check the traction using a piece of paper.

There are two options for turning off a floor-standing gas boiler. You can turn off only the main burner or the main burner together with the pilot

Switching on the floor-standing boiler:

  • The door of the device is opened, the position of the boiler control knob is checked in the off position.
  • The gas supply valve opens.
  • The control knob is set to the piezo ignition position.
  • Next, press the handle for 5 - 10 seconds so that the gas passes through the pipes and displaces the air. The piezo ignition button is pressed.
  • Then the presence of a flame in the burner is checked. If the burner does not light, the procedure is repeated.

After igniting the main burner, you can use the control knob to adjust the heating temperature.

User manual

There is no doubt that Lemax boilers can show their best side. But a lot depends on the consumers themselves, whether they comply with the instructions or not

And the most important thing begins even before the moment when there is a need to light the installed boiler. It is required to choose strictly equipment that matches the power of the heated room

Since exceeding the operating pressure is very dangerous, it is imperative to install a relief valve and set it properly.

The following actions are not allowed:

  • introducing water into the system while the combustion chamber is running, as well as after it is stopped - until the coolant cools to less than +50 degrees;
  • using a boiler when circulating coolant cooled to +50 degrees or less;
  • use of heating devices with automatic components without grounding;
  • installation of gas boilers, their commissioning, prevention and any technical manipulations by persons who do not have official permission;
  • the use of devices in conjunction with smoke ducts that do not correspond to them;
  • covering ventilation duct grilles.

You can turn on any boiler from the “Premium” collection or another series only after connecting it to the chimney; be sure to also prevent it from blocking and disrupting normal draft. You should also check that the entire heating system is filled with water, that it is not blocked anywhere by valves or air pockets. In the event of a serious failure of the automation, you should immediately turn off the boiler, and also leave all attempts to start it until the defects are eliminated by professionals. If the coolant warms up to more than +95 degrees, the boiler is also turned off and the cause of overheating is eliminated independently or with the help of hired specialists.

In advance, at the stage of selecting and installing equipment, it is necessary to prepare high-quality natural ventilation. It is recommended to install a steel sheet not only in front of the firebox, but also under the boiler itself, as well as around it around the perimeter.

If there was already a boiler or stove installed before, then during installation without replacing pipes and radiators, they should be washed. Violation of this requirement means that all claims regarding pipe capacity, heating of the coolant and the room, and water circulation will not be accepted. When starting up a gas boiler, first turn the knob and only after that start adjusting and starting. The time to initiate gas ignition ranges from 10 to 60 seconds, depending on a number of parameters that are unpredictable in a particular case. After the end of the annual heating phase, you cannot drain the water from the boiler itself and the heating lines - this threatens rapid and severe corrosion.

Catalytic emitters

The key feature of gas burners with catalytic emitters is their extremely high efficiency, which reaches almost 100%. To make the heating element, fiberglass is used, which is subsequently coated with a platinum layer.

Catalytic heaters are fireproof and environmentally friendly - fuel burns without open fire, so there are no harmful emissions. The working process is almost silent, and the air heating rate is quite high, so the entire volume of the tent heats up very quickly.

The cost of such devices directly depends on their power, and the difference in price can be quite noticeable. In addition, the catalytic safe tent heater only works on branded cartridges, for which you also have to pay.

Important Operating Instructions

In terms of operation, gas boilers with a closed combustion chamber are considered safer. Their firebox does not communicate with the room air. However, the power of such boilers is significantly inferior to the power of boilers with an open combustion chamber. Therefore, in private households a second type of boiler is often installed.

The choice of future coolant depends on the goals and operating conditions of the system. If the boiler is expected to be turned off frequently, then it makes sense to think about using antifreeze

The operation of such boilers requires compliance with safety precautions. So, to install a powerful floor-standing boiler, it is customary to use a separate room with a certain size. The boiler is mounted at some distance from the walls. Nearby walls should be protected with fire-resistant material to prevent fire.

A ventilation system must be installed in the boiler room. There should also be a source of natural light. The width of the entrance door must be at least 80 centimeters. The chimney is laid in accordance with the instructions for the boiler and from heat-resistant material. The chimney must rise above the roof ridge by at least half a meter.

One safety measure is to install carbon monoxide detectors. The gas detector will promptly detect the leak of a volatile toxin and warn users about it. It can also be configured so that the ventilation is automatically turned on and the gas supply is turned off. Modern automation allows the implementation of a variety of smart systems.

If the temperature, pressure or gas sensor fails, you must immediately turn off the boiler and call a service technician. Using a boiler without these devices is fraught with serious negative consequences.

SNiP requirements state that a gas boiler must be connected to the main line using a copper pipe or a bellows hose. In this case, a faucet must be installed

If signs of a gas leak are detected, you must immediately turn off the gas tap and open the windows to ventilate the room. Do not turn on the light and try to illuminate the room by lighting matches or a lighter.

The gas boiler must be serviced at intervals specified by the manufacturer. Information about the necessary procedures is indicated in the instructions for the device. For example, you need to clean the chimney, remove scale from the heat exchanger, or clear the fumes from the burner. Then the boiler will last a long time, and the risk of serious malfunctions will be significantly reduced.

When using a gas device, do not turn it on at maximum power for a long time. This may result in the release of steam, which is unacceptable.

Sometimes the boiler begins to make unusual noises and vibrations. This may be due to the operation of the fan. We warn you that all actions that require disassembling the boiler casing automatically deprive the owner of the right to warranty repair or replacement.

However, the owner of the unit needs to monitor the operation of mechanisms and systems that protect the boiler from fire. It is necessary to maintain the temperature in the circuits at around 50 degrees, which significantly reduces the likelihood of mineral deposits forming on the internal surfaces of pipes and devices.

Wood stove for home heating

Brick stoves are a traditional Russian way of heating homes.

The oldest method of heating a residential home is using a wood stove. Traditionally, such a stove was made of brick. In modern houses, firewood is more often used to start a fire, and then coal, peat or some other fuel is loaded into the firebox. Firewood is also used to maintain fire in fireplaces, which serve more to create comfort than to fully heat a residential building consisting of several rooms. Thus, a wood stove is almost an anachronism, and this type of fuel is usually used in combination with some other type to heat a house.

Finding a good stove maker these days is quite difficult. But it is necessary to lay out a brick oven in compliance with the finest nuances.

How to start a gas boiler: preparation

There are simple instructions explaining how to start the gas boiler shown in the photo. The initial start-up is carried out when the installation and wiring of all elements of the heating equipment is completed, and the correctness of the work has been verified by the relevant authorities.

The location of the heating unit must be selected in accordance with safety standards and regulations that prevent fires. The boiler must be located at a certain distance from the wall, which depends on the manufacturer's recommendations. By the way, for some models of gas appliances this requirement is not relevant. You should also make sure that there are no flammable materials or objects nearby.

When solving the problem of how to start a gas boiler, special attention should be paid to the supply of pipes from the gas main. They do not carry out this installation work themselves, but invite specialists from the relevant services who are involved in connecting, sealing and, if necessary, installing a gas meter

After this, the boiler is connected to the chimney pipe, in which the draft and its performance are checked. She must go outside. The installation work to install the chimney depends on the type of heating device.

When preparing for startup, the boiler is disconnected from the power supply to fill it and the heating system with cold water. Then they check for leaks, turn the thermostat to the maximum value so that the operating mode switch lights up in automatic mode.

Starting the boiler after the summer. Stages of the first start-up of a gas boiler

After purchasing a gas device, the question arises of how to start a gas boiler. The first start is performed after the unit is installed and all communications are connected to it. Installation must be carried out in accordance with all norms and regulations.

Representatives of the gas supply company must be present when the unit is started.

Stages of starting a gas boiler

Answering the question of how to properly start a gas boiler, it should be said that the gas heating system is turned on step by step in accordance with the instructions.

Filling with water

First, fill the heating system with water. To do this, a special valve is unscrewed at the bottom of the unit. By unscrewing it, they begin to supply water to the pipes and radiators. At the same time, it is necessary to monitor the pressure gauge. The pressure should be at 2 atm.

If the first start-up of the unit occurs during the cold season, then it is advisable to preheat the room to 18-20ºC.

When the required pressure inside the system is reached, the air remaining inside the radiators and pipes should be released.

Bleeding air

Excess air accumulated in radiators reduces their heat output, so it is important to get rid of it immediately. To effectively release air, during installation of the system, each radiator should be equipped with a Mayevsky valve

They are very convenient for removing excess oxygen from certain areas. When you open a tap, you can usually hear hissing and whistling noises. If instead of hissing water begins to come out, then there is no air lock in this place

To effectively release air, during the installation of the system, each radiator should be equipped with a Mayevsky valve. They are very convenient for removing excess oxygen from certain areas. When you open a tap, you can usually hear hissing and whistling noises. If instead of hissing water begins to come out, then there is no air lock in this place.

After releasing air, the pressure may drop, so you should check the pressure gauge and add coolant if necessary.

Sometimes the problem is trapped air inside the pump. Some devices are equipped with an automatic reset system. But usually it is not very effective, so before starting it is better to perform this manipulation manually:

  1. Remove the front cover from the housing, find the pump - its location is indicated in the instructions.
  2. To bleed air from the circulation pump, plug the boiler into a power outlet and start heating the water. A noise like gurgling sounds may appear - this is how the air makes noise.
  3. Take a screwdriver and unscrew the plug. When water starts flowing, the plug must be installed back. This manipulation should be done several times until the gurgling disappears.

After releasing air from the circulation pump, check the pressure gauge reading. If the pressure has dropped significantly, it should be increased.

Pressure testing and flushing of the system

It would not be superfluous to carry out pressure testing and flushing of the heating system. After these procedures, the user will be confident that the inside of the pipes is clean and there are no leaks.

Pressure testing is done to ensure there are no leaks. To perform this, a pressure pump is required. With its help, air or water is pumped under pressure, then a break is taken for 10 minutes. If after pressure testing the pressure does not decrease, then the system is reliable and sealed. If the indicator has decreased, you should look for the “weak spot” and eliminate the leak.

Flushing is performed to clean the heating system of all contaminants and debris. To do this, open all the taps on the batteries, place containers under them and supply water under a pressure of 4 bar. The flow of water will cleanse the system of rust and sediment. For heavily contaminated radiators, flushing is carried out several times.

First start

The first start-up of a gas boiler must be carried out by a gas service specialist. You can do the preparatory work before starting the gas heating boiler yourself, but connecting the gas main must be carried out by a specialist - a gas fitter. Subsequently, if everything went well, he issues a certificate that allows you to operate the gas boiler.

For automated models, for example, “Vailant”, “Beretta”, “Ferroli”, starting involves the following sequence of actions: plugging in, opening the gas valve, pressing the start button, setting the required temperature.

When piezo ignition, hold down the flame regulator for a few seconds, then press the ignition button.

Construction of Lemax boilers

Lemax boilers are a welded structure, inside of which are located:

  • heat exchanger;
  • gas burner device with control unit;
  • combustion chamber;
  • thermostat;
  • gas outlet and threaded pipes.

Depending on the model, the heat exchanger can be made of copper tubes or cast iron. The gas burner device is located in the opening of the combustion chamber and is used to turn on the boiler. The thermostat sets the temperature and maintains it. Installed on the front panel. For ease of control, the regulator is equipped with divisions. The gas outlet pipe is responsible for removing combustion products and is located in the upper part of the unit. The boiler is connected to the heating and water supply system through threaded pipes located on the rear of the housing.

Important! The ignition process takes no more than a minute. If after this time the burner does not light, then you need to look for a malfunction problem

Before turning on the boiler, it is necessary to check it for the presence of draft and water both in it and in the heating system. Next, you need to open the gas valve and follow one of the instructions below. How to turn on a Lemax boiler depends on whether it is equipped with piezo ignition or not.

Connection by piezo ignition

It is easy to start such a unit. You just need to follow three steps:

  1. Turn the control knob to the ignition position.
  2. Press it all the way and hold it until the burner lights up. Usually 10-60 seconds is enough.
  3. Set the temperature mode.

Connecting with a match or gas lighter

You can light the Lemax boiler with matches; how to do this is described below:

  1. Turn the thermostat knob to position “0”.
  2. Through the viewing window, bring the flame of a match or gas lighter to the igniter.
  3. Press and hold the ignition button until the igniter lights up.
  4. Next, to ignite the main burner, you need to set the thermostat knob to position “4”.
  5. Then you can set the desired temperature.

To turn off, turn the knob to the “Off” position.

Important! The ignition process takes no more than a minute. If after this time the burner does not light, then you need to look for a malfunction problem

What devices use bimetal?

The scope of application of the bimetallic strip is extremely wide. Almost all devices where temperature control is necessary are equipped with bimetal-based thermostats. This is explained by the design simplicity and reliability of such relay systems. In our usual technology, thermostats are:

  • In household heating appliances: stoves, ironing systems, boilers, electric kettles, etc.
  • Heating systems: electric convectors, gas and solid fuel boilers with electronics.
  • In electric packages there is automatic shutdown.
  • In electronics in measuring instruments, as well as in pulse generators and time relays.
  • In thermal engines.

In industrial technology, bimetallic plates are installed in thermal relays designed to protect powerful electrical devices from temperature overloads: transformers, electric motors, pumps, etc.

Malfunctions and their causes

Sometimes when using gas boilers, malfunctions occur. This is true not only for older models, but also for those that have served their owners for a relatively short time.

Here is a list of the most common problems:

  • the boiler does not turn on;
  • the unit switches off very often;
  • in some cases you can see that it has completely gone out;
  • the boiler turns off completely or goes out very quickly, resulting in smoke;
  • The burner does not light well and it takes a long time to turn on.

It is necessary to consider why this happens and what to do in these cases.

  • For example, if the draft in the boiler is broken or there is no draft at all, then a constant flame cannot be maintained. To check the presence of draft, you need to light a match and carefully bring it to a special testing window. If there is traction, the fire will deviate in any direction. If it is not there, then the fire will burn quite evenly. If there are such problems, then you need to clean the chimney.
  • Sometimes the draft, on the contrary, is too great, in which case the flame will also die out. This can also be corrected: it is necessary to install dampers to reduce traction.
  • There are cases when the chimney shaft becomes covered with ice, which interferes with the full circulation of water. This usually happens in very cold winters. To solve the problem, you first need to knock off all the ice, and then insulate the pipe from the outside. After this, the system should work without interruption.
  • If the burner does not light up for a very long time, the reason may be a faulty sensor. To understand whether this is so, it is necessary to short-circuit the opposite terminals with each other; if nothing lights up, you need to change the sensor.
  • There are times when smoke comes out from behind the boiler door. This occurs if the gas does not ignite immediately. To eliminate this problem, you need to adjust the air flow to the burner. To do this, you just need to find the adjusting washer and move it in one direction or another.
  • Injectors often fail. This usually happens during repair work, then the gas flows partially. To eliminate this problem, you need to either repair the nozzle or replace it with a new part.
  • It happens that in warm weather gas boilers can fail. The reason is that the temperature outside and in the chimney are different. To prevent this from happening, you need to warm up the chimney at least from time to time.

Connecting a room thermostat

A room thermostat is a convenient and useful device that allows you to regulate the temperature of the air, not the coolant, in the heating system. The default sensor monitors the outlet temperature of the heating agent.

This does not give a correct picture of the state of the microclimate in the room. For example, when the outside temperature rises, the room becomes hot.

But the sensor cannot track this, and the extract air temperature is within the limits specified by the mode, so from the point of view of the system, everything goes fine, in accordance with the boiler settings.

If a room thermostat is used, the burner will turn off much earlier, which will improve the microclimate in the room and significantly reduce gas consumption.

To connect the room thermostat, you need to set the boiler's own element to the maximum temperature.

It will only work as a limiter when overheating. The external unit is connected at one end to the automation unit, and at the other to the boiler thermostat. By default, a jumper is installed between the contacts, which must be removed and the thermostat connected.

IMPORTANT!

It is necessary to use the appropriate brands, for example - CEWAL RQ10. Installation of a thermostat is only possible on boilers marked N (with the SIT 820 NOVA automation unit).

Construction of Lemax boilers

Lemax boilers are a welded structure, inside of which are located:

  • heat exchanger;
  • gas burner device with control unit;
  • combustion chamber;
  • thermostat;
  • gas outlet and threaded pipes.

Depending on the model, the heat exchanger can be made of copper tubes or cast iron. The gas burner device is located in the opening of the combustion chamber and is used to turn on the boiler. The thermostat sets the temperature and maintains it. Installed on the front panel. For ease of control, the regulator is equipped with divisions. The gas outlet pipe is responsible for removing combustion products and is located in the upper part of the unit. The boiler is connected to the heating and water supply system through threaded pipes located on the rear of the housing.

Important! The ignition process takes no more than a minute. If after this time the burner does not light, then you need to look for a malfunction problem

Before turning on the boiler, it is necessary to check it for the presence of draft and water both in it and in the heating system. Next, you need to open the gas valve and follow one of the instructions below. How to turn on a Lemax boiler depends on whether it is equipped with piezo ignition or not.

Connection by piezo ignition

It is easy to start such a unit. You just need to follow three steps:

  1. Turn the control knob to the ignition position.
  2. Press it all the way and hold it until the burner lights up. Usually 10-60 seconds is enough.
  3. Set the temperature mode.

Connecting with a match or gas lighter

You can light the Lemax boiler with matches; how to do this is described below:

  1. Turn the thermostat knob to position “0”.
  2. Through the viewing window, bring the flame of a match or gas lighter to the igniter.
  3. Press and hold the ignition button until the igniter lights up.
  4. Next, to ignite the main burner, you need to set the thermostat knob to position “4”.
  5. Then you can set the desired temperature.

To turn off, turn the knob to the “Off” position.

Important! The ignition process takes no more than a minute. If after this time the burner does not light, then you need to look for a malfunction problem

Ignition of coal in pyrolysis boilers

If you plan to fire boilers with coal, you should always pay attention to the type of grate, because there are special modifications for each type of fuel.
Many manufacturers often include grates for coal in the kit. Ignition of coal depends on whether the long-burning device has been used before and whether it has automatic controls for regulating the air supply. The main element of automation is the fan.

It is carried out like this:

  1. Open the scrambling door (second from the bottom) and place paper on the grate. Place thin paper or newspaper correctly.
  2. Special wood chips for ignition are poured onto the paper. It doesn't take much.
  3. Small firewood is placed on top.
  4. Crushed coal is placed on the firewood. Its consumption is high. The layer thickness should be 15 cm.
  5. The damper in the chimney is opened completely.
  6. They light the paper, close each door and turn on the automation, setting the required temperature level.
  7. After 5-10 minutes, check how the fire has flared up. To do this, turn off the automation and open the combustion door. It is better to open it slowly as the smoke output will be small. If the first portion of coal does not ignite, then close the door, turn on the automation and wait some more time. If the coal catches fire, the main portion of fuel is poured on top. Sprinkle correctly so that the cracks in the front part of the grate remain uncovered.

What devices use bimetal?

The scope of application of the bimetallic strip is extremely wide. Almost all devices where temperature control is necessary are equipped with bimetal-based thermostats. This is explained by the design simplicity and reliability of such relay systems. In our usual technology, thermostats are:

  • In household heating appliances: stoves, ironing systems, boilers, electric kettles, etc.
  • Heating systems: electric convectors, gas and solid fuel boilers with electronics.
  • In electric packages there is automatic shutdown.
  • In electronics in measuring instruments, as well as in pulse generators and time relays.
  • In thermal engines.

In industrial technology, bimetallic plates are installed in thermal relays designed to protect powerful electrical devices from temperature overloads: transformers, electric motors, pumps, etc.

Electronic boiler

The Lemax line of boilers, which connect to a 220V network, is actively expanding and now includes wall-mounted double-circuit Prime models, as well as floor-standing Clever and Wise.

Unlike imported competitors, whose control boards often burn out due to power surges, these devices are designed to operate in Russian networks.


Wall-mounted boilers, as a rule, have a built-in circulation pump, an expansion tank and significantly more control and protection systems

However, such models can sometimes fail.

To ensure safety, the main protection systems are still mechanical:

  • a thermocouple controls combustion and shuts off the gas if the burner goes out - error E1;
  • the draft sensor gives a signal to shut down if combustion products are not removed - error E3;
  • the membrane gas valve will shut off the fuel supply if its pressure drops below critical, or the gas is turned off in the network - error E1;
  • The overheating thermostat controls the temperature of the heating circuit; if it overheats, it turns off the boiler with error E2.

All these systems are designed in the same way as in mechanically controlled boilers, and their location depends on the model. Therefore, we will not re-describe the inspection and repair of each component, but the instructions for it will help you find them in your boiler.

In addition, an electronically controlled boiler will not start if it detects a malfunction of any of its boards or sensors, or their unsatisfactory readings - for example, low water pressure or a supply voltage of less than 170V.

To avoid having to go through the entire boiler, the location of the fault will be indicated by the error code and its explanation in the instructions.


To set up and repair electronic controls, it is better to contact a specialist; he can resolder, reflash or replace the board

If the boiler does not react at all to an attempt to turn on, even the screen does not light up, most likely there is a problem with the power supply. As trivial as it may seem, check whether the plug is plugged into the socket, whether the machine is raised, whether there is any light in the house at all.

A child could pull out the plug from the socket, and the machine could turn off due to a voltage drop, so do not neglect this advice.

If the power supply is normal and the boiler display does not light up, call the service department for diagnostics and repair or replacement of electronic control elements.

Malfunctions and their causes

Sometimes when using gas boilers, malfunctions occur. This is true not only for older models, but also for those that have served their owners for a relatively short time.

Here is a list of the most common problems:

  • the boiler does not turn on;
  • the unit switches off very often;
  • in some cases you can see that it has completely gone out;
  • the boiler turns off completely or goes out very quickly, resulting in smoke;
  • The burner does not light well and it takes a long time to turn on.

It is necessary to consider why this happens and what to do in these cases.

  • For example, if the draft in the boiler is broken or there is no draft at all, then a constant flame cannot be maintained. To check the presence of draft, you need to light a match and carefully bring it to a special testing window. If there is traction, the fire will deviate in any direction. If it is not there, then the fire will burn quite evenly. If there are such problems, then you need to clean the chimney.
  • Sometimes the draft, on the contrary, is too great, in which case the flame will also die out. This can also be corrected: it is necessary to install dampers to reduce traction.
  • There are cases when the chimney shaft becomes covered with ice, which interferes with the full circulation of water. This usually happens in very cold winters. To solve the problem, you first need to knock off all the ice, and then insulate the pipe from the outside. After this, the system should work without interruption.

  • If the burner does not light up for a very long time, the reason may be a faulty sensor. To understand whether this is so, it is necessary to short-circuit the opposite terminals with each other; if nothing lights up, you need to change the sensor.
  • There are times when smoke comes out from behind the boiler door. This occurs if the gas does not ignite immediately. To eliminate this problem, you need to adjust the air flow to the burner. To do this, you just need to find the adjusting washer and move it in one direction or another.

  • Injectors often fail. This usually happens during repair work, then the gas flows partially. To eliminate this problem, you need to either repair the nozzle or replace it with a new part.
  • It happens that in warm weather gas boilers can fail. The reason is that the temperature outside and in the chimney are different. To prevent this from happening, you need to warm up the chimney at least from time to time.

Why is blood pressure rising?

If the pressure in the system increases, this usually indicates that the water level has increased. This problem can lead to serious emergencies and even an explosion of a cast iron radiator. To reduce risks, the installation included an expansion tank that collects excess water.

An increase in pressure indicates problems with the tank. Problems can occur in the membrane, which sag in order to make room for an increased volume of water. Sometimes it breaks, and can also be loosely fixed to the walls. As the volume of fluid increases, there will be nowhere for it to go, which will cause an increase in pressure.

The situation can be corrected by replacing the membrane or the expansion tank itself (if that is the problem).

Basic faults

There are several possible reasons why the Lemax gas boiler goes out or does not start at all:

  • A gas leak has been detected. In this situation, you need to immediately open the windows wide, turn off the gas, and turn off the device itself. You also need to call emergency services.
  • Insufficient draft, burner clogged. The signal will be a red tint of the light, elongation of the reeds and their smoking. Eliminate the cause by cleaning the chimney and burner.
  • If there are other difficulties with the chimney and thermostat, the main burner may involuntarily turn off.
  • There is no water circulation. With an existing pump, the pipeline slope may be set incorrectly.
  • The gas was turned off. In this case, the equipment will turn off spontaneously.

Which boiler from the model range to choose

Consumers have a somewhat contradictory opinion about Lemax boilers: some praise them for their unpretentiousness, inexpensive maintenance and reliability, others criticize them for the occasional failures and malfunctions. The manufacturer has been manufacturing heating systems for decades - this alone deserves trust. As for problems, as the experience of service center workers shows, they occur in almost all models and depend little on the brand.

When choosing a unit, owners should consider the following conditions:

  • the boiler must have a power reserve;
  • 1 kW approximately corresponds to 10 m2 of heated area;
  • level of heat loss in the house.

The range of heating equipment is constantly expanding, new, productive and reliable products are appearing. The obvious advantages of Lemax brand boilers include the fact that a solid repair base has been formed for them, the main “problem” areas have been identified and the restoration of faulty equipment is not a problem. Moreover, most major problems can be fixed at home, without turning to specialists for help.

Rating
( 1 rating, average 4 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]