How to turn off a gas boiler for the summer: general principles

Modern gas boilers are highly efficient, reliable equipment that can operate for decades. All this will depend on how accurately users carry out routine maintenance of the boiler unit, prescribed by state regulations, rules and factory instructions. A situation where the user is faced with the question of how to turn off a gas boiler can arise for various reasons: a timely shutdown for the summer due to the end of the heating season, an emergency shutdown or commissioning work. Basically, this procedure is not complicated; it depends on the specific device, the purpose of stopping and the level of automation of thermal processes.

Commissioning of a floor-standing boiler

Introductory information

Automation EuroSit 630 is a multifunctional device that regulates the gas supply. It provides the ability to regulate the temperature and completely turn off the main burner.

Purpose:

  • automatic adjustment of gas supply;
  • control of the safety of gas equipment.

It is worth noting the difficult method of turning on the device. In his defense, we can say that in this way the manufacturer was concerned about the safety of its consumer and the safety of gas equipment.

Start of a gas boiler

The operation of a gas boiler begins with the start of the automation. In the situation of using the 630 EuroSit valve, the startup process will consist of several stages. They should be performed in accordance with the established order:

  • turning on the tap on the riser;
  • turning on the pilot burner;
  • turning on the main burner;
  • temperature adjustment and setting.

Step-by-step description of the startup procedure

The first step is to turn on the gas supply to the system. To do this, you need to open the tap on the riser.

Now you can start working on the gas valve. To do this, you need to concentrate on the control handle of the device. Initially, it is located in the “off” position. It must be moved to the “ignition” position (image of fire on the regulator). After this, you need to press the handle so that the forced supply of gas to the pilot (ignition) burner begins. Now you should press the piezo ignition button while continuing to hold the handle pressed. The presence of a flame on the pilot burner indicates that everything was done correctly. The handle should be kept pressed for the next ten seconds after pressing and while checking for the presence of flame. This must be done to start the gas boiler mechanism.

After ten seconds, you need to release the control handle and check again for the presence of a flame on the pilot burner. If there is no flame on the burner, then all the operations described above should be repeated. In this case, you will have to increase the time you press the control handle.

If there is a flame on the pilot burner, then you can proceed to ignite the main burner. To do this, the control handle must be moved to position from “1” to “2”, turning it counterclockwise. The correctness of the actions will be indicated by the appearance of a flame from the main burner. After making sure that it is present, the control handle can be moved to positions from “1” to “7”. The position must be selected based on the coolant temperature needed to be obtained. In the situation with the EuroSit 630 model, the number 7 on the handle corresponds to a temperature of 90 degrees. This is the maximum possible value for the model. By following all these steps, starting the gas boiler will go without problems.

Disabling a device

To turn off the gas boiler, you must turn off the gas valve. There are two shutdown options:

  • turning off the main burner;
  • turning off the main and pilot burners.

In the first case, the control handle must be turned clockwise and set in the “ignition” position. The main burner will then be switched off, but the pilot burner will continue to operate.

In the second case, the same control knob must be turned clockwise until the “off” position is reached. These actions will stop supplying gas to all burners. A click will sound to confirm that the device is turned off. The flame will also disappear. The gas supply has now been stopped.

Principle of operation

The principle of operation of the gas boiler draft sensor is to timely send a signal to the valve, which shuts off the gas supply to the burner. The device is triggered if there is a disruption in the flow of combustible products in the correct and natural direction (from the boiler equipment through the chimney to the street). Otherwise, smoke from carbon monoxide, carbon dioxide, water vapor, and soot will penetrate into the house where the boiler is located and can harm human health.

It is not difficult to understand how the sensor works. Everything is based on the standard laws of physics. It is a bimetallic relay that works to turn the boiler on/off. Inside the thermostat there is a metal strip that reacts to changes in temperature

The next thing that the user should know is that the fixture is adjusted to the temperature according to the fuel that is used. If it is natural gas, then the temperature is 75-950 °C. If liquefied gas is used, then 75-1500 °C.

If the sensor senses that the draft in the gas equipment is very poor, then it will increase heating of the smoke gases and subsequent blocking will turn off (immediately, after a few minutes after switching on).

In gas boilers with an open combustion chamber (atmospheric units), a safety thermostat controls the presence of draft and the temperature of the flue gases; with a closed combustion chamber (turbocharged units), the pressure of the air blown out by the turbine.

Is it necessary to turn off the gas heating boiler at all?

If there is no urgent need for this, we do not recommend doing this. The potential gas savings are actually quite small. Or absent altogether. Yes, sometimes you can save a few cubes, but this negatively affects the performance of modern equipment. The reason is that it is during the startup and shutdown process that the system is subjected to the heaviest load. Accordingly, heating equipment wears out faster. If shutdown is still necessary, then there should be long intervals between several turns on.

Starting up after the coolant has completely cooled down has a particularly detrimental effect on the system. For example, if you turned off the boiler for the weekend and the coolant (water) has completely cooled down during this time. In this case, after ignition, condensation may form on the heat exchanger and burner. And over time, it can cause equipment failure.

Many owners, in an effort to save money, do not turn off the floor-standing or wall-mounted boiler, but only tighten the gas valve. Firstly, this is ineffective, and secondly, it also has a bad effect on the operation of the equipment. Gas burners can only operate properly at a certain level of gas pressure. If the pressure drops, the burner can continue to operate, but the fire will move noticeably closer to it, reducing its service life.

Important!

We strongly advise against changing the factory settings of any gas equipment.

Where do we start?

A household gas boiler is a powerful and efficient device designed to heat the coolant and circulate the heated liquid through the heating system of the house. Modern boilers heat not only batteries, but also tap water in large volumes, have electronic controls and various safety mechanisms. When purchasing a boiler, you should pay attention to the heating area so that it is slightly larger than your living space.

Naturally, you have already installed the unit itself and made all the necessary connections and piping of the heating system. We checked the chimney and draft, as well as the device itself for proper operation and absence of leaks. This stage of work, as a rule, takes place in the presence of gas industry employees, who carefully record all the results and “give the go-ahead” for the use of this device.

Some models of domestic gas boilers are very demanding to install. It is necessary to strictly comply with the instructions in the instructions - maintain a distance from the wall, do not install the device near windows or at an angle. Now you can start starting the heating.

Before starting the boiler itself, it is necessary to fill the heating system - pipes and radiators - with coolant, that is, water. To do this, unscrew the valve at the bottom of the boiler. For different boiler models, the “appearance” of this supply valve may be different, but it cannot be confused with anything else. As a last resort, check the instructions for your device.

By opening the valve, we will begin to supply water to the pipes and radiators. Be sure to monitor the pressure level, wait for the mark of 2 - 2.5 atm. This indicator can be measured using the pressure gauge built into the boiler.

If the first start-up of a gas boiler occurs in the cold season, it is better to preheat the premises using alternative heaters and supply “summer” water - about 18-20°.

When the required pressure inside the system is reached, it is necessary to bleed off the air that may remain inside the batteries and pipes. Air locks significantly worsen the heat transfer of your battery, is this the result you are trying to achieve?

To quickly and effectively bleed air, you need to unscrew the Mayevsky taps on each battery. At first, you will hear a whistling or hissing sound - this is normal. If water starts running out of the radiator, it means there is no air lock.

Bleed the air from the battery that is the highest in level.

When you have checked all heating devices, look at what the boiler pressure gauge now shows. The pressure will probably drop slightly and you will need to top up the heating system with water.

But in addition to plugs in the pipes, the normal operation of the boiler can be prevented by the air inside the circulation pump. This is easy to fix. Some models are equipped with an automatic air release system, but, as a rule, it is not effective enough, so it is better to get rid of the air manually the first time.

To do this, remove the front cover from the boiler body, then look for the pump itself - a cylindrical part with a plug for a flat-head screwdriver. Sometimes, the pump is located behind the dashboard, which is easily moved away or removed from the closures. To release air from the pump, turn on the boiler and start heating the water. The boiler will start up. The pump will also begin to engage in the working process - this will be confirmed by incomprehensible gurgling sounds inside the unit - do not be alarmed, this is air. Take a flathead screwdriver and slowly unscrew the plug. When water flows, screw the plug back. This procedure should be carried out several times. When you stop hearing the gurgling of water inside the device and your gas boiler starts working, it means that you have managed to completely get rid of the air inside the pump. At this stage, you should again check the pressure gauge readings with the instructions for the device. In principle, you can stop there - now your boiler will heat water inside the radiators, and if it is a double-circuit unit, then in the water supply.

After starting the boiler, the distant batteries are turned on to maximum, and the near ones are screwed down. For this purpose, special regulator valves are used, which are installed on the radiator inlet pipe. After debugging the heating system, you can set a comfortable temperature for the batteries.

But it would not be amiss to carry out pressure testing and flushing of the heating system. After these procedures, you will be 100% sure that the inside of the radiators is clean and your heating system has no leaks.

Reasons for turning off the gas boiler

A gas boiler is the real “heart” of a private home. It provides the building with heat, and double-circuit models with hot water.

Thanks to the electronic filling, the main processes - turning on, turning off, switching to another mode, adjusting the temperature - are carried out automatically, without human intervention. The owner needs to set the program by pressing, depending on the manufacturer’s instructions, the appropriate buttons or keys.

Gas boilers are preferred because of the cheapest fuel - gas. Solid fuel units or wood stoves are more often installed if there is no gas main nearby

Shutting down may be necessary for various reasons:

  • moving to another place of residence;
  • seasonal shutdown for the warm period;
  • emergency shutdown due to boiler breakdown and the impossibility of quick repair or replacement;
  • planned stop for maintenance - removing deposits, flushing the internal circuit or cleaning soot;
  • connection of other heating or hot water equipment;
  • disabling one of the functions - for example, heating, etc.

Most often you need to turn off the heating. To do this, the operation of 1-circuit units is completely stopped, and for 2-circuit units, only one line is shut off - the heating line.


Double-circuit models perform 2 functions: heating and hot water. Since hot water is also required in the summer, the water heating circuit is left in operation, and the hot water supply line continues to be operated as usual

Many modern models have the option of switching to summer mode . At the same time, the boilers do not fail - they also continue to work, maintaining the optimal temperature and keeping the system “ready” for active start-up at any time.

In summer, especially in the northern regions, there are also cold snaps and even frosts, so the existing equipment turns out to be useful.

Step-by-step instructions for disabling

If the gas burner does not light or goes out immediately after switching on, automatic shutdown often occurs for inexplicable reasons, popping noises occur, the temperature of the water in the circuit does not correspond to the indicators, noise uncharacteristic for the operation of the unit is heard, there is a water leak in the housing, the pressure drops - the equipment should be turned off immediately .


If, upon entering the house, you smell gas, do not turn on the lights, electrical appliances or light a fire. Immediately call your service provider, turn off the equipment and turn off the gas

The shutdown procedure for boilers is carried out differently, but the main stages are similar.

Using the Baxi model as an example, let’s look at how to properly and quickly turn off a gas boiler:

  1. Shut off the fuel supply by turning the gas shut-off valve.
  2. Leave the fan running for another 15 minutes.
  3. Turn off the fan, stop the smoke extraction system.
  4. Wait until the temperature in the circuit is below +30 °C and turn off the circulation pump.
  5. Turn off the power by turning the switch to the “Off”, “0” or other position specified by the manufacturer.
  6. Carry out conservation work on the boiler and related equipment.

Not all systems drain the water completely. Some manufacturers recommend adding a liquid to the coolant that prevents the formation of lime deposits. Propylene glycol or antifreeze are recognized as the most effective for household communications .

When force majeure situations occur, you have to quickly figure out how to quickly turn off the gas boiler, while maintaining the functionality of the system and not harming yourself. Next we will consider special cases.

Sometimes, when there is overheating or lack of draft, the boiler automatically turns off. It stops working, and accordingly, the heating of the house stops. If automatic shutdown occurs very often, 5 times in 15 minutes, you should turn off the gas and contact the service department.


When gas equipment automatically turns off, an error code is displayed on the electronic display. In this case, you need to find this code in the instructions and act according to the manufacturer’s recommendations

Problems in the smoke removal system also automatically stop the unit. It usually shows an error on the display and stops working for 12-15 minutes and then turns back on. If the problems are not resolved during this time, an automatic shutdown occurs again - and so on until the problem is completely eliminated. To clean the gas exhaust channel, turn off the gas and turn off the boiler.

Many boilers are protected from freezing by automatic means. The protection works if the boiler sensors are connected to the power supply, the system pressure is normal and the gas is not shut off.

In case of any malfunction, if the temperature of the coolant in the circuit drops below + 8-10 ° C (depending on the model), the operation of the unit is suspended. As a last resort, if you cannot quickly cope with the circumstances - turn on the boiler and get it functioning - you can try to drain the water so that the pipes and parts of the unit do not rupture.

Crimping

For this procedure you will need a pressure pump. You don’t have to buy it - most likely, you won’t need it anymore. You can borrow such an instrument from friends or rent it. Pressure testing can be carried out with a powerful air stream or a water jet with increased pressure and take a 10-minute pause. You do this to detect leaks if they exist. If after the operation your operating pressure on the boiler

did not decrease - the system is absolutely reliable and sealed. If the pressure is below operating pressure, you should look for a leak.

Unlocking the emergency state of the boiler

  1. Use the heating temperature control knob on the boiler instrument panel to set the temperature to maximum.
  2. Then sharply turn off the temperature regulator to zero.
  3. We repeat the procedure 2-3 times, turning the sensor either to maximum or to minimum.
  4. We leave the regulator in the maximum temperature position and wait for the boiler to automatically unlock. The system should start automatically.
  5. We wait until the emergency stop light of the device goes out.
  6. After such manipulations, set the regulator to the desired temperature.

Unlocking is complete.

Operating principle of the boiler

Heaters operating on gas fuel may differ from each other in design and technical characteristics, they all use the same principle - heating the working environment of the heating system using burning fuel, in our case natural gas.

Gas is used not only for space heating, but also for heating water. For this purpose, either water columns or double-circuit boilers are used. The equipment used these days is equipped with highly effective safety systems - they keep the gas combustion process under control. But, nevertheless, there are mandatory rules for the use of gas equipment and compliance with them can become a guarantee of safety.

Before putting the equipment into operation, the user must ensure:

  1. There is the required amount of working fluid in the heating system.
  2. The fact that the burner and safety valve are in working order.
  3. Measuring instruments show correct data.
  4. The operating temperature of the boiler device should not fall below 65 degrees. This may lead to condensation.

Conclusion

Of course, only the user will decide what is more convenient for him, but boiler manufacturers advise first inviting an engineer to assess the volumes and calculate what installation is needed. After all, sometimes there is no point in installing a huge, expensive heating system, and sometimes it is an absolute necessity.

The newest models of gas boilers are characterized by high power and heating speed. However, their prices are steep, to put it mildly. You can try to use a more economical option and install new automation on the old boiler or fix the old one. The operating principle and automatic design of old-style gas heating boilers will be explained in this article.

Requirements for use

Before you start using the boiler, you need to make sure of some very important points. The heating system must have the right amount of fluid. The boiler itself must be connected to the atmosphere through an expansion tank. The safety valve and burner field must be in working order. The latter should be freed from foreign objects and other debris. The boiler valve must be opened.

Before starting ignition, it is necessary to remove the protective film, if any, from the burner. How is ignition carried out? First you need to make sure that there is no smell of gas in the room. In addition, such phenomena as an open pipeline supply valve and the presence of draft in the chimney are unacceptable. Immediately before ignition, the burner viewing window opens. The burners bring fire to the middle of the field. If ignition has occurred, a slight pop should appear. As a rule, this happens within 5-7 seconds.

If, after these steps, ignition still does not occur, then you should immediately turn off the valve and ventilate the room. The next attempt can be made no earlier than 10 minutes later. This is what the operating rules say.

The temperature during boiler operation must not fall below 65°C, as this may lead to condensation.

It is important to ensure that no specific gas odor arises in the room during work. At the same time, the temperature cannot be higher than 90°C

The boiler burner must be periodically cleaned of dirt.

This is what the basic operating instructions for this unit look like. It is important to be careful when using a gas boiler and not to deviate from the rules of use. Use it correctly!

Is it possible to disable

When installing the sensor and using gas equipment, you can often observe periodic shutdowns in operation. In this case, you may want to turn off the traction device completely. However, there is no need to rush.

Draft sensor for gas boiler AOGV and AKGV

There are several reasons for this:

  1. Firstly, a sensor disconnection may indicate poor traction performance. Weak intensity of movement of smoke gases leads to overturning of the draft in boiler equipment. Harmful fumes will enter the house in large quantities.
  2. Secondly, the problem may be backdraft. An air lock forms. The exhaust gases of the smoke move to a certain point in the chimney and then fall back. This occurs due to poor heating of the pipe and poor thermal insulation.

Of course, theoretically it is possible to disable the sensor, but this entails great danger. If an emergency suddenly arises, there will be no protection. Therefore, it is not recommended to operate a gas unit without such a controller.

Accommodation requirements

These requirements will directly apply to the room in which the gas boiler is to be located. What does the instruction manual say about this? Thus, the room must have a total area of ​​more than 7.5 m². Ceiling height - at least 2.2 m.

Diagram of a gas boiler from Vaillant.

In addition, the room must have a window that can be opened if necessary. It should go outside. This is required by fire safety.

As for the door in this room, it should open in the direction of movement from the room. There should be no switches in the room itself. They should be moved outside the room.

A ventilation system (supply and exhaust) is required. Approximately 15 m² of air per 1 m² of gas burned is required. Three air exchanges are also needed.

When installing the boiler itself in a room, fire safety precautions must be strictly observed. So, from the boiler to the combustible elements of the room, you need to measure a distance of no less than 25 cm. As for non-combustible elements, a distance of 5 cm is allowed here.

The distance between the chimney and combustible parts is 40 cm, and between the chimney and non-combustible parts - 15 cm.

The gas boiler must be installed on a perfectly flat surface on which there are no slopes

This is important for safe use.

Additional recovery steps

Be sure to ventilate the heating system, i.e. Bleed the air from the radiators at all points in the house where you have taps. Don't forget about the heated towel rail (if it has a tap).

If an automatic air vent valve is installed at the top heating point (circled in the photo), then you need to loosen the cap to allow the air to escape

On the boiler, check the water pressure in the system again so that it is at least 1.5 bar at the start of operation. This is the minimum operating pressure in all gas boilers while the water in the pipes is still cold. As the liquid heats up, the pressure will become higher. It is advisable that it does not exceed 2.5 bar. Too much pressure is harmful to the connecting elements of the system (oil seals, cuffs, etc.), which can simply be torn out by the force of water. If the sensor shows higher than the maximum number in your technical data sheet, drain some water from the pipes and check the pressure again.

The last stage of installation of almost any heating system is its first trial run, debugging and commissioning. By and large, if boiler equipment is started up for the first time, then this work is a priority for service centers. During the first start-up, service center specialists check the correct connection of the boiler, perform its debugging and put this equipment under warranty. If you carry out the first launch yourself, then you can’t count on a warranty service center. Starting and debugging the heating system can also be done while the system is in operation - you won’t have to turn to specialists every time. Owners of individual heating simply need to know this process. We will study it with you in this master class with step-by-step photos, in which, together with the website, we will study in detail the issues of how to start the boiler and how to debug the heating system with your own hands.

Service life

The service life of gas equipment is determined in the technical passport of the boiler and ranges from 10 to 15 years. However, with regular maintenance and prevention, it can last much longer. The regulatory services may establish additional requirements for service life.

This may be due to the presence (or absence) of spare parts that are needed in the process of maintaining full operation of the boiler. If during the repair some part is required, and the manufacturer has stopped producing them, it may be necessary to replace the boiler as a whole with a more modern one and one equipped with spare parts.

Distinctive features

The Vulcan gas boiler is produced in the Ukrainian city of Kharkov. The equipment is presented by two lines of floor-standing boilers designed to supply heat to residential buildings and other premises.

Key features of Vulcan floor-standing gas boilers:

  • long service life: with proper care and compliance with operating requirements, units can successfully operate for 15 years or more;
  • the burners are made of stainless steel, which indicates their strength and reliability;
  • high performance: efficiency is 90%;
  • combustion chamber - open or closed type;
  • The equipment can effectively cope with the heating of rooms whose area reaches 300 m².

Based on the type of chimney, Vulcan boilers are traditional and parapet.

An important advantage of heating devices is that they are completely independent from the electrical network.

You can read more about parapet gas boilers in this article.

Commissioning of a wall-mounted boiler

For installation and initial start-up of a wall-mounted gas boiler, it is better to contact the organization of the specifics in question. The presence of all approvals and appropriate qualifications for the installation of water heating equipment on the part of the service center will allow you to purchase a warranty, as well as extend it with proper operation in subsequent years. All this must be accompanied by documentation in the form of an act or card with a stamp and signature.

In addition to the provided warranty, when contacting specialists, another advantage is the safe installation and adjustment for economical operation of the gas boiler. Safety means the absence of gas leakage and the risk of unwanted ignition.

Installation features

According to SNiP requirements, the heating boiler must be connected to the gas main using a copper pipe or a stainless steel bellows hose. The presence of a gas shut-off valve is mandatory. It is also possible to use various types of adapters and fittings for connection. We must not forget about the presence of gaskets and sealing materials at the joints.

Gas boilers can only be mounted on fireproof walls at a distance of at least 2 centimeters. Otherwise, a fireproof material (plaster, metal or ceramics) must be placed between the boiler and the wall. The distance to the wall should be more than 3 centimeters, and the sheet area should exceed the dimensions of the heating installation in width and height.

Another important condition for placing a gas boiler is the presence of a hood and a window with elements of free air access. After installing the heating boiler, it is necessary to check for gas leaks using an electronic device or a soap solution.

Commissioning

The sequence of actions when starting a wall-mounted gas boiler may differ slightly and be as follows:

  • The mains voltage is measured. If there is a large “drawdown”, operation of the water heating installation is possible with the additional inclusion of stabilizing devices;
  • Check the tightness of the expansion tank using a pressure gauge (preferably before filling the heating system with water). The pressure in a diaphragm-type tank should be slightly less than in the heating system. Air pumping is possible (with water drained from the boiler);
  • The circulation pump is being prepared. To do this, unscrew the screw representing the plug and located in the center. The engine rotor rotates to avoid unwanted blocking (jamming as a result of long-term storage) and subsequent failure. The cover screw is screwed back in;
  • All taps open (including the “feed” tap);
  • After filling the heating system with water and reaching a pressure of 1.2 - 1.5 bar, the “make-up” tap is closed;
  • The power cord is connected;
  • The plug of the automatic air valve on the circulation pump is opened;
  • Using the control unit, the forced operating mode of the pump is activated. At this time, the heating system is “de-aired” (air is bleed through the radiators);
  • Check the pressure in the gas line (if possible);
  • The operation of a gas heating boiler is checked in all modes (hot water supply and heating) at different temperature setpoints;
  • Temperature is monitored using indicators;
  • The gas supply, maximum temperature of the heating circuit and hot water supply are adjusted based on the criteria of efficiency and durability.

How a double circuit does not stop working: winter and summer mode | Heat monster

Heating technology is mainly of interest to owners of houses outside the city, where there is no hot water supply and individual heating is provided. To provide themselves with specific comfort conditions, the owners of such houses have to either install a water heater and a single-circuit boiler and water heater, or a double-circuit boiler. The latter type of equipment allows you to simultaneously obtain hot water for use in domestic tasks and purposes and ensure productive operation of the heating system in winter.

Scheme of a gas water heater.

The double-circuit unit is a special design, which provides its advantages, making it possible to use it to obtain the required volume of hot water in a short period. To understand exactly how this equipment keeps running, you need to consider it in comparison to other types of heating equipment.

Types of heating boilers

Diagram of the circulation system of a gas water heater.

The choice of new equipment that can be used for TENA in a heating system is extremely wide. The market for boiler room equipment shows different models from manufacturers in different countries. Still, all the variety can be divided into only two categories according to installation option (wall or floor) and type of construction (single-circuit or double-circuit).

A wall-mounted gas boiler is more compact than a floor-standing one, which often requires equipment in a separate room (boiler room). The differentiation of boilers by the number of heating circuits indicates their practical capabilities. In the first version, a gas boiler is used only for heating, and in the second, two heating circuits are built in, which is why they are also used to provide hot water. In this case, both circuits operate independently of one another, in other words, if you need to heat the water, this will not at all affect the efficiency and quality of the heat supply.

Installation of gas equipment for heating

The design principle of all gas-powered boilers is similar. They may differ in details that do not affect the overall scheme of work.

Each gas boiler is a warm body, the thermal insulation layer in which prevents the loss of heat energy that appears during gas combustion.

The housing contains practical details:

Connection diagram for a two-stage gas boiler.

The specifics of the shape and design of the burner are related to the energy carrier used. In gas boilers, this is a chamber; in the middle of it, thermal energy is released when gas burns and various oxides appear (in this case, combustion products). The burner is necessary to generate energy, which is used to heat the coolant of the heating system.

The pipe coil is a structural component placed above the burner with the heat carrier in the middle. In many systems, water is used as a coolant, but it can also be antifreeze. Gaseous, liquid and solid substances, simultaneously with the resulting heat, move from the burner to the pipe coil, its walls are heated, and with them the coolant. It begins its own movement through the system, thanks to it the room is heated, and the cooled combustion products are sent to the chimney and discharged outside.

Gas boilers can transfer heat in different ways, depending on the properties of their design they can be:

  • bithermic;
  • plate (or double).

The last type of heat exchangers consists of two parts. The part intended for the heating circuit consists of plates and copper pipes, which are coated with a special layer that prevents the formation of rust. The main function of such an element of a gas water heater is heat transfer. The second part provides water heating for household needs. It consists of plates that transfer heat to the heated environment. Such heat exchangers are called plate heat exchangers because of their design.

A bithermal pipe coil is 2 pipes, one of which is located in the middle of the other. The internal part of such a structure is necessary to ensure hot water supply, and the external part is necessary for heating.

A gas boiler has certain operating properties depending on the type of ignition with which it is equipped. There are two different types:

  • piezo ignition;
  • electric ignition

Diagram of the working principle of a gas water heater.

The type of ignition device provides the specifics of fuel combustion. It is worth considering different options for air supply to the fuel combustion site. Air from both indoors and outdoors can be used. In the first case, the firebox is open, and in the other, it is closed. In the latter option, natural or mechanical ventilation may be provided.

The operation of different fan components is controlled automatically. Modern gas boilers are equipped with automation based on a microprocessor system. As a result, you can set a specific operating program for the device and all its parameters will be configured automatically.

Working principle of two-stage gas boiler

The gas boiler is designed in a similar way, which will operate in 2 modes: heat supply and hot water supply. When heating a room in the boiler body, a pipe coil with a coolant is heated. It is capable of warming up to temperatures ranging from 35 to 80°, depending on the result you need.

To turn on the heating mode, the gas boiler is equipped with a thermostatic valve that responds to a decrease in temperature in the room. At the same time, it transmits a signal to the system, due to which the pump is started, creating a vacuum in the water supply of the return supply of the coolant. Thanks to this, the heated coolant penetrates the heating system. If the system pressure reaches 0.45 bar or rises above this mark, the relay contacts close and the burner starts to operate. The start of these processes is controlled by the processor.

Diagram of a gas water heater with a fan.

The first time after starting, the gas boiler does not stop operating at low power, which gradually increases to the highest power. If, in the process of increasing power, the coolant is heated to the required temperature, then the power does not increase further and the operation of the device goes into modulation mode. If immediately after startup the operating power of the device is very high, the burner is switched off electronically. You can re-ignite it no earlier than after 3 minutes.

The burner occupies the lower part of the firebox, which is an iron container with high-quality thermal insulation. A pipe coil is placed above it. The burner starts working at the moment when, in order to continue proper operation of the system, it is necessary to heat the water, which in this case is used as a coolant. Along with the operation of the burner, the operation of the circular pump also begins, which ensures the movement of the coolant through the pipeline of the heating system.

When the default boiler operating parameters are reached, the gas supply will be reduced and the boiler will go into standby mode. When the temperature drops again, the temperature sensor will give a signal, which leads to a saturated gas supply, causing the burner to ignite.

Water from the heating circuit does not penetrate into the hot water supply circuit thanks to the three-way valve. The coolant enters the heating system pipeline through the supply pipes and returns through the return pipes. In other words, in the first heat exchanger, water moves in a closed circle. As a result, a small amount of plaque forms on the surface inside the pipes. Water is supplied to the second circuit from the water metering unit; it generally contains much more impurities, which increases the likelihood of circuit failure. If this happens, the boiler can be used as a single-circuit boiler, in other words, only for heating.

Operation of a gas water heater in summer

Diagram of single-circuit and double-circuit boilers.

In summer there is no need to warm up the room, but you still need access to hot water for household needs. In such a case, you can use a double-circuit in summer mode. In this case, the operating principle of the device will be slightly different. The heat supply line is closed by a three-way valve and water from the heating system enters the secondary pipe coil instead of the primary one.

As the water moves through the secondary pipe coil, it receives heat and is fed into the hot water circuit. This process can be started using a pressure switch. When water consumption begins to increase to 2.5 liters, the relay closes. In this case, a signal is sent to the burner, after which it ignites. The fuel supply valve opens, the operation of the device starts, at the initial stage of which the power is not high, but with a gradual increase it can reach the highest level over some time.

Similarly, the device does not stop working until the water is heated to a specific temperature, which you can set on your own. After which the boiler goes into an operating mode in which smooth temperature control of the water is performed.

The intensity of the burner changes automatically and depends on individual water consumption. It turns off when the water temperature exceeds the set temperature by 5°C and turns on again when it decreases by 1°C. During summer operation, the heating circuit does not operate. All the heat received from the burner goes to heating the coolant, which maintains its own immobility, and from it to the water supply circuit.

Pros of two-stage devices

Opting for this type of heating equipment will bring you many benefits. First of all, it is necessary to note the opportunity to save on the purchase of equipment for hot water supply. Moreover, both circuits can act independently of each other, in other words, if one of them breaks, the second cannot be harmed. At the same time, replacing a circuit in a two-stage boiler is not very expensive, as is repairing individual appliances used to heat water and heat the room.

Similar devices are quite convenient to use and economical, as they operate on the most inexpensive type of fuel at the time. Such a device is much more compact than two individual devices.

Likewise, the double-circuit does not stop working according to the simplest scheme. The special design makes it possible to perform two tasks at once, the most important for ensuring a comfortable life: home warmth and frequent access to hot water.

Most shared blog posts in seven days

Convector heating pros and cons

One of the main questions of interest to our readers remains the aspect of the feasibility of the purchase. Why a convector, and not an oil radiator, for example? What power characteristics should an electric convector have? How to choose the best among the incredible assortment?

From a certain point of view, any equipment must contain pros and cons; an electric convector is no exception. We will start by listing the positive qualities, especially since they many times exceed the disadvantages of an electric convector.

1. We consider the main advantage to be a technological breakthrough that allows us to design an electric convector with an efficiency of 95%. Agree, paying for electricity and getting zilch as a result would be an unaffordable luxury. A modern convector converts electrical energy into heat with maximum efficiency.

2. The low price for an average 1000 W electric convector is a strong argument in favor of the purchase.

3. Quiet operation. An electric convector does not require a fan or any other mechanically moving structural elements. Silent operation is periodically interrupted by a barely audible click of the temperature sensor, which contributes to more economical operation of the device.

4. Lack of installation and maintenance work. An electric convector is considered a household appliance, connects to a 220-volt network and does not require permits from government organizations. The small mass of the convector is an additional plus when it comes to relocating the device in a heated room

5. Built-in automation helps maintain the required temperature in the heated room. Remote temperature sensors, made like sockets with a thermostat, additionally provide temperature control.

6. The heating element of the electric convector reaches the set temperature in a couple of minutes, starting to heat the room immediately after switching on. The element temperature, as a rule, does not exceed 60 °C, preventing heating elements from “drying” the air and “burning” oxygen. The absolute humidity of the air in the room does not change. As the temperature rises, only the relative humidity decreases slightly.

7. Low heating temperature of facing surfaces provides a safe environment for people and animals. In addition, you don’t have to worry about fire safety.

8. The service life of convectors declared by a number of manufacturers exceeds 20 years.

Electric heating convector probably has one drawback

So you bought a convector and made sure that your wiring can withstand the additional load. The device, connected to the network, instantly begins to heat the room. As they say, there would be no price for an electric convector if not for one BUT. The only negative, as you might have guessed, is the high cost of electricity consumed. But firstly, as we noted at the beginning of the review, the convector heats our apartment only during the off-season, and not throughout the winter.

Secondly, you need to choose electric heating convectors with a thermostat, then the built-in thermostat will not allow the device to “wind the meter” around the clock. Thirdly, care should be taken to preserve heat and, if possible, reduce heat loss; it is necessary to install double-glazed windows and take care of other insulation elements.

Another disadvantage is the smell of combustion; in fact, it is not oxygen that “burns”, but the dust that has settled on the electric heating element. To remove this drawback is as easy as shelling pears, either vacuum the convector, or simply wait until the dust completely burns out.

What is a convector

The market offers a variety of types, where it is quite easy to get confused. Oil radiator, electric convector, infrared emitters, your head is spinning from the range and price offers. We will devote our review to the electric convector. The principle of operation of the convector is based on the physical properties of heat transfer from the coolant, in our case from the heating element to the heated room using internal energy, which is transmitted by jets and flows, that is, by convection.

In simple words, a heating element is built into the convector, which makes the air around it hot. The heated air begins to move upward, making room for cold air flows. This “cycle” is called natural convection. We hope we have answered the question of what a convector is. A picture will help you understand this simple process more clearly:


Operating principle of an electric convector

As we can see, the electric convector has a simple principle of operation. By the way, since air movement occurs due to convection, the device does not require additional equipment with a fan, thus the electric convector earns a plus in its piggy bank. Of course, this is not the only advantage that forces us to choose an electric heating convector to ensure a comfortable climate in our apartment, but first things first.

Why shouldn't you turn off your heating at night?

There are those who, in an effort to save money, turn off the boiler every evening - both single-circuit and double-circuit. They are motivated by the fact that at night, lowering the temperature in the house is acceptable and, in general, even recommended - a person sleeps better at a room temperature of about 20 degrees. But this mode does not affect savings. Or the consumption becomes even higher - during the day the boiler begins to catch up with the lost temperature. And to heat the coolant it uses even more gas than during normal operation. The result is that you will pay even more for heating than with a constantly running boiler.

You need to know that new models of heating equipment turn off themselves when the temperature of the coolant or in the room itself reaches a set value. When the temperature drops, the equipment is activated again.

Likewise, you should not turn off the unit if you are leaving for 1-2 days. As a result, after restarting, it will begin to work harder, will use more gas, and individual elements of the system will wear out more. In some cases, an emergency shutdown is required. Then use the instructions above on how to turn off the boiler. If disconnecting is only of interest to you to save money, then this is not a solution. There are many more efficient ways to save on heating costs.

How a gas boiler doesn't stop working

  • Pros and cons of double-circuit
  • The working principle of a double circuit to heat water with a primary and secondary type pipe coil
  • The working principle of a double circuit to heat water with a bithermal pipe coil
  • Malfunctions and breakdowns

Now there are two types of heating boilers: single-circuit and double-circuit. Single-circuit units can be floor-mounted or wall-mounted and are intended for heating premises. Depending on the power, they can heat rooms of any size. A double-circuit heating system can also heat any room, but it is also intended to heat water. Therefore, such a device will be much more expensive. But you won’t need to spend money on water heating equipment, because... you get a “2 in one” device.

Rice. 1. Hydraulic diagram in heat supply mode: A - Supply line, B - DHW, C - DHW, D - Return line, 1 - Gas burner, 2 - Circulation pump, 3 - Three-way valve, 4 - Secondary pipe coil, 5 - Pipe coil primary coil.

The main work in boilers is performed by:

  • pipe coil;
  • eagle;
  • thermostat;
  • one or two circulation pumps;
  • control device;
  • expansion tank;
  • thermometer;
  • a device for determining pressure.

Pros and cons of double-circuit

The double-circuit unit is the most common and sold on the heating equipment market. Its uniqueness lies in the dual connection of space heating and water heating. A gas boiler, which has two pipe coils, copes with two similar functions.

Let us indicate their main positive qualities:

Rice. 2. Hydraulic diagram in water heating mode: Fig. 2. Hydraulic diagram in water heating mode: A - Heat supply line, B - Hot water supply line, C - tap water, D - Heat supply return line, 1 - Gas burner, 2 - Circulation pump, 3 - Three-way valve, 4 - Pipe secondary coil, 5 - primary pipe coil.

  • when using such devices, gas consumption is significantly reduced;
  • installation is quite simple due to its compactness and light weight;
  • can be installed in any place, which means the boiler does not require a separate room;
  • Quiet operation of the device is ensured by a water system;
  • routine machine maintenance and operation;
  • you can choose a double-circuit to heat water with absolutely any power, which is why both a small room and a large country house can be successfully heated;
  • The device allows you to use hot water without purchasing water heating equipment.

The dual circuit also has disadvantages:

  • Such a heating boiler does not usually perform these 2 functions simultaneously, due to this, when heating the room, the water heating is turned off, and vice versa;
  • heating of the liquid occurs in flow mode, there is no direct connection with a storage electric water heater;
  • It takes up to 1 minute to heat up; before that, cool water will come out of the tap, which means there will be little water loss.

to come back to the beginning

In Fig. Figure 1 shows the hydraulic diagram in heat supply mode. Explanation of the picture:

A. Supply line

D. Return line

  1. Gas stove.
  2. Circulation pump.
  3. Three way valve.
  4. Secondary pipe coil.
  5. Primary pipe coil.

Navien boiler, instructions.

Rice. 3. Diagram of the heat supply mode: A - Supply line, B - DHW, C - Cold water, D - Return line, 1 - Gas burner, 2 - Bithermic pipe coil, 3 - Circulation pump.

During the operating period of the apparatus in heat supply mode, the gas burner transfers heat to the primary pipe coil. The pump circulates the liquid. This means that liquid does not penetrate into the secondary pipe coil due to the three-way valve. The heated liquid leaves through the heating line (A). For subsequent heating, the liquid is returned via (D) the heating return line.

In Fig. Figure 2 shows the hydraulic diagram in water heating mode.

Here the three-way valve closes the heating line. Warm water moves from the primary pipe coil to the secondary one. Tap water (C) is heated as it passes through the secondary pipe coil and enters the hot water supply line (B). There is an advantage of using double-circuit heat exchangers.

Here, ordinary tap water is used, which contains various salts and deposits. From chemistry class we know that as soon as the temperature increases, salts precipitate, thus forming a strong layer of deposits. These deposits clog the pipe coil, interfering with the passage of liquid through the pipes and reducing the service life of the device. However, in the primary heat exchanger, water passes in a closed circle and at the same time it does not change the chemical parameters, thus not exposing the gas boiler to rust. But the fluid passing through the secondary pipe coil puts its own salts in it, which can cause it to get dirty. Due to this, it will need to be repaired or completely replaced over a period of time.

If the second pipe coil breaks, the gas boiler will be able to continue operating in heat supply mode, which plays a big role when it’s cold outside.

The only disadvantage of two-stage boilers is their high cost when compared with devices based on a bithermal pipe coil. Its bad quality can be called double load, because... it needs to work in both heat supply and water heating modes.

In order for a room to be heated to a specific temperature, a thermostat is needed that changes operation depending on the ambient temperature. Whether the device turns on or not depends on whether the liquid has reached the set temperature. To ensure that the device always turns on at the required temperature, you need to adjust the thermostat manually at different periods of time.

to come back to the beginning

Rice. 4. Diagram of the hot water preparation mode: A - Supply line, B - DHW, C - Cold water supply, D - Return line, 1 - Gas burner, 2 - Bithermal pipe coil, 3 - Circulation pump.

In Fig. Figure 3 shows the hydraulic diagram in heat supply mode.

In Fig. Figure 4 shows the hydraulic diagram in the hot water preparation mode.

A. Supply line

D. Return line

  1. Gas stove.
  2. The pipe coil is bithermic.
  3. Circulation pump.

During operation in water heating mode, heat from the gas-powered burner and from the combusted gases is supplied to the coolant, and then to the DHW circuit, but at the same time, the circulation of liquid in the heating circuit stops.

During operation in heat supply mode, heat is supplied to the coolant from combustion products. While the device is operating in water heating mode, heat is supplied to the thermal carrier, and then to the DHW circuit. Fluid movement should not occur in two circuits at the same time.

to come back to the beginning

A gas boiler is a complex system, and the main danger lies in the use of explosive fuel. To control the operation of the boiler, specialized automation is turned on, which changes the ideal operation of the unit. If your boiler doesn't work when you turn it on, make sure someone hasn't accidentally turned on the thermostat. You need to turn it on, set the temperature and wait until it rises to this temperature. You need to check whether the warning light turns on and turn off the gas supply.

If your device does not stop working due to overheating, then in this case the repair of AOGV boilers will consist of cleaning the pipe coil. If your overheating meter trips, you need to immediately turn off the boiler and call a repairman. Prevention, repair and safety

When using boilers to heat water, it is recommended to follow these rules:

  • To prevent scale from appearing in the heat exchanger very quickly, you should use water at a temperature of no more than 45°C;
  • clean the pipe coil once every 2-5 years, depending on the hardness of the water, the heating temperature and the amount of water used;
  • install a filter at the cold water inlet, which should be cleaned and changed occasionally.

As for safety, we recommend buying a gas boiler to heat water with additional safety components. It can be:

  • blocking thermostat that turns off the gas supply if the water overheats;
  • flame meter when the fire dies out, turns off the gas supply;
  • a meter that controls the thrust;
  • shutdown device when the liquid level is insufficient;
  • blockers that are triggered when the electrical power supply changes, when the gas supply is turned off, when the water supply is turned off.

Methods for preserving gas boilers

Let's consider the main methods of preserving heating equipment, but with one caveat - not all are used in home maintenance. Some of the methods are more suitable for equipment installed in production plant workshops.


For home maintenance, alkalis are used - caustic or soda ash. It is not recommended to use acidic reagents on your own; hydrochloric or sulfuric acid can only be used by qualified specialists

The process of preservation of the heating circuit is preceded by a preparatory stage, which includes several points:

  • Disconnecting the boiler from the gas main and central water supply, installing plugs. If water is supplied by the pumping station, the pump stops.
  • Removing water or other coolant from the system.
  • Cleaning internal surfaces from scale.
  • Washing boiler parts and circuit.

Professional cleaning of calcium deposits can only be carried out by specialists - and the service organization has such a service. There are two most effective and simple ways to remove scale - chemical , mechanical (manual cleaning), but the first is recognized as the most effective.

The internal parts of the boiler, on which large deposits have appeared, are ground with a power tool, and scale in hard-to-reach places is removed manually, with brushes or scrapers.

Method #1 - dry stop

Dry preservation is carried out in production, usually for maintenance activities or during routine inspections, when it is necessary to stop production for up to 30 days. It consists of completely freeing equipment and pipelines from liquid and further drying.


The procedure is called "dry stop". It is applicable to any models of boilers, regardless of pressure, but is contraindicated for units in which the drums are connected to the pipeline with rolling connections

Procedure:

  • Natural coolant cooling.
  • Stopping the boiler.
  • Displacement of liquid under pressure of 0.8-1.0 MPa.
  • Drying the system naturally or by ventilation.
  • Installation of trays with desiccants in the collectors - quicklime or calcium chloride grains.
  • Closing the firebox and flue, plugs - complete sealing of the system.

At home, water is drained through special taps installed at the bottom of the pipeline. Then they carry out repair or maintenance work and leave the equipment in a “dry” state until the next heating season.


The drain valve is a shut-off valve that must be installed when installing a heating system. Most often, brass models are used, selected according to the diameter of the pipe.

The circuits are refilled with coolant using a pump. The heating function is activated only after the pipeline has been completely filled with water, circulation has been checked and diagnostics have been carried out.

This method is the only correct one if it is necessary to stop the boiler operation for the winter or for an even longer period.

Method #2 - wet preservation option

I use wet preservation if I need to stop the boiler for a short period. The main goal is to keep the equipment in working condition, protect against corrosion, and prevent oxygen from entering the circuit.


To fill pipes at home, a special liquid is used that prevents the formation of rust. It is sold in specialized stores in concentrated or ready-to-use form.

For regions with severe frosts, liquids that do not freeze at low temperatures are used. For example, concentrated antifreeze is in a liquid state down to -60 °C. To prevent the substance from thickening, it is diluted with water. But we must remember that the freezing point of an aqueous solution increases.

Antifreeze has other disadvantages:

  • “eats” rubber;
  • has a high degree of fluidity;
  • cannot tolerate overheating - turns into acid;
  • expensive.

Instead of antifreeze, use a solution of sodium sulfate at a rate of 10 g/liter of water. The liquid poured into the system is heated to displace the air, and then all holes are hermetically sealed. A pressure test pump is used to pump water into the circuit.

Method #3 - gas preservation

For private houses, the gas preservation method is not used, since this requires special equipment and professional skills.

The essence of the technology is that gas is released into the pipes, which, when in contact with metal, unlike oxygen, does not cause corrosion. Such gases include argon , ammonia , helium , and nitrogen .


Some types of gas are hazardous to health, and without following safety regulations, you can easily get poisoned or get burned. All procedures are carried out strictly according to the instructions and in protective clothing.

The conservation process is complex and is carried out in several stages:

  • the system is washed with deaerated water;
  • connect a gas cylinder and a pressure reducer;
  • fill the circuit with gas, displacing water;
  • close the drain valve;
  • when the indicator is 0.013 MPa, the gas supply is stopped;
  • close the pipe, turn off the cylinder.

The main condition for gas preservation is the absence of air in the system , so throughout the entire period of inactivity it is necessary to monitor its tightness.

Method #4 - applying excess pressure

High-pressure preservation technology is usually used in enterprises where all conditions are created for this. It is used for water heating and steam equipment.


The main task is to prevent oxygen from entering the system. To do this, a pressure above atmospheric is created inside the circuit, while the usual coolant is replaced with deaerated water

The overpressure method is suitable if it is necessary to stop the operation of a gas boiler for a short period of time - up to 10 days. Typically, during this period, repair work not related to water heating equipment is carried out.

What rules must be followed?

When carrying out measures to preserve boilers in production, they are guided by the requirements set out in RD 34.20.591-97 “Guidelines for the preservation of thermal mechanical equipment.”

The same standards should be observed by owners of equipment installed in private homes.


If you are not confident in your knowledge or skills, contact your service organization. Specialists will carry out work to shut down the boiler and preserve the equipment in compliance with all safety requirements

What you need to remember if you decide to mothball your heating or hot water equipment yourself:

  • Before any repair work, the gas must be shut off. The main valve is installed at the gas pipeline entry into the house.
  • Even the slightest ingress of oxygen into the system will cause corrosion of boiler parts and pipelines, so you need to choose one of the preservation methods and follow it strictly according to the instructions.
  • When working with chemical reagents, you must protect your body parts with thick clothing, wear comfortable shoes, gloves and a mask.
  • To keep the pipes and components of the unit in working condition, it is necessary to observe the dosage when diluting concentrated compounds and dry chemicals.
  • Work with explosive or flammable substances may only be carried out by specialists.
  • Upon completion of work, it is necessary to turn off the power supply to additional equipment - for example, a pump.

The above rules must be followed to protect your own health and preserve the equipment.

After a long period of inactivity, the heating and water heating system will require re-preservation - a process that also requires compliance with certain rules.

Safety system

Gas-powered appliances require serious monitoring. It is provided either by a person or an automation system. The latter is capable of providing multi-stage protection that prevents dangerous situations and increases equipment safety. The main task of the protection system is to turn off the device in time by stopping the fuel supply.

Let's look at the stages of protection using the example of the Proterm Wolf KSO floor-standing boiler. These modern devices have multi-stage protection. One of the stages is an ionization sensor that controls the flame. If the fire goes out, a signal will be sent to the control unit, it will shut off the fuel supply and prevent an accident.

The combustion chamber has a temperature sensor that monitors the heating of the coolant and prevents the firebox from quickly burning out. “Wolves” are equipped with a KTD system - chimney draft control. It prevents the accumulation of carbon monoxide. If there is no draft, combustion products begin to accumulate in the chimney, and the thermostat heats up. When the temperature limit is reached, the thermostat contacts open and the flow of fuel stops.

Automatic protection

Modern heater models are equipped with electronic control and measuring instruments that generate signals for the control unit. Automation, receiving signals from sensors, coordinates the work of all nodes. Elements that prevent various types of malfunctions and problems are safety valves, expansion tanks, air valves, smoke detectors and other devices.

What does it look like and where is it located?

According to the gas safety rules PB 12-368-00, domestic heating boilers must be equipped with a draft sensor. The installation site, as a rule, is the smoke hood (located in the smoke extractor) or the free space between the ventilation duct and the unit body.


In atmospheric boilers, the draft sensor has a slightly different appearance.

It is worth paying attention that it cannot be attached closely to the surface of the flue. Paronite gaskets are used as a “separator”: this measure reduces the likelihood of contact heating, as well as creates a gap that will provide technical access to the flue opening and to the draft sensor.

What to do if problems occur

Let's look at breakdown situations using the example of Italian Baxi boilers. Italian wall and floor heaters are an example of quality and efficiency. But even with proper use, malfunctions may arise that require prompt correction.

The following problems may appear in Baksi models:

  • the burner does not light;
  • during operation, popping noises are heard in the firebox;
  • the boiler overheated;
  • the device is very noisy;
  • The sensor has failed.

The probable causes of breakdowns are associated both with violations of operating rules and with reasons beyond the control of the user:

  • moisture has entered the device;
  • low quality coolant;
  • the pressure in the gas pipeline has decreased;
  • voltage drop in the electrical network;
  • errors were made during installation.

Violation of at least one rule or norm leads to breakdowns, incorrect operation and unnecessary costs.

What does it look like and where is it located?

According to the gas safety rules PB 12-368-00, domestic heating boilers must be equipped with a draft sensor. The installation site, as a rule, is the smoke hood (located in the smoke extractor) or the free space between the ventilation duct and the unit body.

In atmospheric boilers, the draft sensor has a slightly different appearance.

It is worth paying attention that it cannot be attached closely to the surface of the flue. Paronite gaskets are used as a “separator”: this measure reduces the likelihood of contact heating, as well as creates a gap that will provide technical access to the flue opening and to the draft sensor.

Recommendations and tips for caring for the boiler after switching off

The heating system, led by the boiler, is a large and complex mechanism that provides the home with heat and hot water. In winter, it is almost impossible to live without this in a private house, especially in the harsh Russian climate. But you need to prepare for the heating season in the summer after the boiler is turned off.

Note! First of all, annual preventive measures significantly reduce the risk of accidents and breakdowns.

Also, such frequent work meets safety standards. Anyone who has gas equipment at home should know the main stages of preventive maintenance:

  • visual inspection of all systems.
  • cleaning all parts of the mechanism.
  • cleaning the inside.
  • burner regulation.

These activities are in most cases carried out by specialists. At home, these operations are carried out independently as follows:

  • The coolant is drained from the entire system, and not just from the boiler.
  • visual inspection of the entire system.
  • the location of structural units that must be replaced is determined.
  • replacing gaskets.
  • removal of deposits and scale.
  • lubrication of the circulation pump and forced ventilation fan.
  • The most important point: checking for gas fuel leaks.

Turning off the boiler in the summer is not always necessary. The feasibility of this event is assessed by the owner independently. The choice to turn off the home fire or not depends, first of all, on the brand and type of boiler.

How to remove air pockets?

Simply connecting the system by filling it with water is not enough. It will not work or its effectiveness will become extremely low. To carry out a full first start-up of the equipment, it is necessary to bleed all the air that has accumulated in it from the system. A modern gas boiler may have a special system for automatically releasing air when filling, but the efficiency of such systems is low. This means that manual bleeding of the main and other systems is required during connection. Only after this can you start.

Removing air pockets during connection is carried out not only in the circulation pump, boiler, but also in all heating radiators. In this case, it is recommended to start the process with radiators. Especially for this purpose, they are equipped with so-called Mayevsky taps, which you simply need to open by placing a basin under them. At first, a slight whistle will be heard - this is the air gradually leaving the system. If the plugs are removed, water begins to flow. If the batteries are free of air masses, then the taps must be closed. This simplest procedure is carried out with each radiator; it must be checked and cleared of plugs. When air has been removed from all radiators, the pressure gauge needle will be set to the desired value. Before turning on the gas boiler, you need to add coolant to the system, that is, feed it with liquid.

Next, you need to completely remove all air pockets from the circulation pump, which requires disassembling some parts of the boiler. This work is simple, you just need to remove the front panel of the boiler, and then find a cylindrical part that has a lid in the middle of the body, it has a slot for a screwdriver. The boiler must be started, that is, power must be supplied, and the heating regulator must be set to the required operating position. After this, a faint hum will be heard - this will start the circulation pump. You can hear gurgling and other sounds. Using a screwdriver, you need to slightly unscrew the lid of the found part; this should be done until water flows out. As soon as the liquid begins to seep out, the lid must be screwed back on. This procedure needs to be carried out 2-3 times, after which the air pockets will completely leave the system, the sounds and gurgling will disappear, and the pump will begin to operate quietly. Immediately after this, the electrical ignition of the equipment will work, and the gas boiler will begin to operate independently.

The pressure in the heating system must be equalized by adding water to the required level. The system gradually warms up and begins to enter normal operating mode. Connection and first start-up for any heating equipment is a complex and demanding process. How effective the heating will be depends on proper preparation, startup, and adjustment of the system.

How to choose?

Options for the material of manufacture of the heat exchanger - the container where the coolant is heated:

  • Steel. Good ductility, minimizing the likelihood of cracks due to thermal stress. Used in budget models. The service life is short due to susceptibility to corrosion.
  • Cast iron. Heavy weight. They cost more than steel ones. Minus - they react to temperature changes. They don't rust - a plus. They serve for about half a century.
  • Copper. They weigh little. Corrosion resistant. They are usually found in wall-mounted versions.

Rating
( 2 ratings, average 4.5 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]